F.3 Configuration via the Profibus-DP master systems pro-
ject
A GSD-File is part of the delivery. This file is used by the respective Profibus master system to
define the application’s specific parameter data set and the configuration data set for each
Profibus slave which work together with the RM 96xx.
These data sets are produced via a master-specific project tool. The Profibus master uses
these data sets when starting the bus system to set e.g. the characteristics of the Smart_DP
module.
The Smart_DP module could be configured as a ‘Radio Master’-module or as a Radio Slave’-
module which are described in the following sections.
F.3.1 Definition of the parameter data set for a ‘Radio Master’
The GSD file contains the following parameters (projecting via a master specific software):
Parameters (Display projecting tool) Configurable parameters Description
All inputs 0 Timeout_Mode
Hold old values
Defines how input data of the slave should behave, if a
NO_LINK-Timeout occurs.
Timeout NO_LINK-Diag Unsigned Integer:
Value in ms.
Values between 1000 ms
and 65536 ms are allowed.
Defines the timeout time to the polled radio slave until diag-
nose information is set on Profibus.
Modem Guard Time
Recommended: 200ms
Unsigned Integer:
Value in ms.
Values between 0 ms and
65500 ms are allowed.
Defines the time which must keep before a new radio slave
could be selected.
Timeout_Mode (Bool): This parameter defines, how the profibus input data of the profibus
slave should behave, if a NO_LINK-Timeout is detected. The selection „All inputs 0“ sets all
input data to zero, whereas the selection „Hold old values“ saves the last values in the register
area.
Timeout NO_LINK-Diag (Integer value in ms): Defines how long no data from the radio slave
station can be received until a diagnose information (NO_LINK-Diag) is set onto the profibus.
Modem Guard Time (Integer value in ms): Defines how long the radio master module must
wait until it try to connect the next radio slave module.
Please refer to point G - „Configuration of the RDT RM96XX-modem“.
Important note:
These defined settings (project data) are sent through the profibus master during
network startup.