User's Manual
ControlPanelLEDIndicato rMessageInterpretation
“OnlyForFixtures(XS&XL)withBatteryBack‐Up”
DiagnosticLEDFunction DiagnosticLED
DiagnosticFAILED RED:On
DiagnosticPASSED GREEN:On
Diagnosticin PROGRESS
Alternate Flashing
betweenREDandGREEN
Tobeincompliancewith NFPALifeSafetyCode101,endusersmustperforma30‐secondmonthlyfunctional
testanda90‐minuteannualtest.The30‐secondmonthlytestisdonebypressingtheDiagnosticTestButton
onthecontrolpanel.A30‐secondself‐diagnostictestisbuilt
intotheprogrammingofthisunit.After30‐
secondstheresultswillbedisplayedasindicatedinthetablebelow.Toconducttheannualtest,power
shouldbesecuredtothestairwellfixturesexternally(i.e.thecircuitbreaker).Attheendof90minutesthe
fixturesshouldstillbeproviding
adequateilluminationthroughtheintegratedbatteryback‐upsystemwithin
thisfixture(ifsoequipped).Thetestitselfandtheresultsshouldberecordedandthisrecord maintainedby
theenduser.ThetablebelowexplainswhattheDiagnosticLEDIndicator(DIAG)means:
StatusLEDFunction StatusLED
ACPowerGood,BatteryCharged GREEN:On
ACPowerGood,Battery
Charging
GREEN:Flashing
ACPowerOff,BatteryGood RED: On
AC PowerOff,BatteryLow RED:Flashing
BatteryFAULT
Alternate Flashingbetween
REDandGREEN
Oncethefixturehasbeenproperlysecuredtotheceilingandpowered,twoIndicatorLEDscanbeseenonthe
controlpanelonthesideofthefixture.Theonetotheleft(whenlookingatthecontrolpanel)isthe
DiagnosticLEDIndicator.Theonetotherightis
theStatusLEDIndicator.TheseLEDsarebi‐colored,meaning
theycanbe2differentcolors,inthiscaseRED orGREEN.ThetablebelowexplainswhattheStatusLED
Indicatormeans:
8
Note:Forfulldetailsrelatedtoperiodictestingofstairwellfixtures,seeNFPA101(00),Sec7.9.3.
XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.com
ArtemisSeriesofLowOccupancyLED
CeilingMountedFixtures(IncludingStairwells)
Installation&OperationGuide
or
XL
ZONEX10AREAX1
or
XL
ZONEX10AREAX1
STAIRWELLX10FLOORX1
TEST
DIAG.STATUS
TEST
DIAG.STATUS
XL
ZONEX10AREAX1
STAIRWELLX10FLOORX1
TEST
DIAG.STATUS
TEST
DIAG.STATUS