User's Manual

ControlPanelForStairwell(XS)Fixtures
FloorX1DialSwitch:
Thisdialissetto
indicatethefloora
particularfixtureis
beinginstalledon.If
thefixtureisbeing
installedonthe4
th
floor,thisdialwould
besetto“4”.Ifthe
fixtureisbeing
installedonthe23
rd
floorthisdialwouldbe
setto“3”,etc.
StairwellDialSwitch:Some
buildingshavemorethanone
stairwell.Thisswitchhelpsto
keepfixturesinonestairwell
fromtalkingtofixturesin
anotherstairwell.Ifyouhave
onestairwell,useasmall
straightslotscrewdriverand
setthedialto
“1”.Formultiple
stairwellswithinabuilding,set
thedialaccordingly.
Timer:Oncethefixtureseesmotionwithinthe
stairwellitwillimmediatelyilluminatetofullintensity.
Asmallscrewdriverisusedtoadjustthe“Timer”.
ThisTimeradjuststhelengthoftimethatthefixture
remainsonatfullpower
priortoreturningtothe
“DIM”setting.TurningtheTimerallthewaytothe
left(counterclockwise)willkeepthefixtureonat
highpowerforonly10seconds.TurningtheTimerall
thewaytotheright(clockwise)willkeepthelightson
atfullpowerfor5
minutesafterthesensorseesits
lastmotion.Thetimecanalsobesetanywhere
between10secondsand5minutesbypositioning
theTimeraccordingly.
StatusIndicatorLED:Thisisa
bicoloredLED(RedorGreen).
ThisLEDprovidestheoperator
withthecurrentsystemstatus.
Seethetable
onthenextpage
foradetaileddescriptionof
thevariousindications.
SelfDiagnostic:Periodicallyit’sagood
ideafortheoperatorstopushtheSelf
Diagnosticbuttontorunthebuiltin
testingprogram.ResultsoftheSelf
Diagnostictestarereportedonthe
“DIAG”LEDIndicator.Seethetable
on
thenextpageforadetaileddescription
oftheindications.
SelfDiagnosticStatusLED:Thisis
abicoloredLEDs(RedorGreen).
ThisLEDprovidetheoperator
withtheselfdiagnosticteststatus
andresults.Seethetableonthe
nextpageforadetailed
descriptionoftheindications.

6
FloorX10DialSwitch:This
dialissettoindicatethe
flooraparticularfixtureis
beinginstalledon.Ifthe
fixtureisbeinginstalledon
floors1‐ 9,thisdialwould
besetto“0”.Ifthefixture
isbeinginstalledonfloors
10 19,thisdialwouldbe
set
to“1”.Ifitisbeing
installedonfloors20 29,
thisdialwouldbesetto“2”,
etc.
EXAMPLE#1:Ifafixtureisbeinginstalledinthesecondstairwellofabuildingonthe17
th
floor,thedialindicators
wouldbesetlikethis:217.
EXAMPLE#2:Ifafixtureisbeinginstalledinabuildingwithonlyonestairwellonthelandingbetweenfloors5and
6,thedialindicatorswouldbesetlikethis:105.
NOTE:Landingsbetweenfloorsshouldhave
thesamedialsettingsasthefloorjustbelowit…i.e.Afixtureinstalled
onalandingbetweenfloors2and3shouldhavethesamedialsettingsasthefixtureonfloor2.
XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone9546178170*Fax9545719777*www.xeleum.com
ArtemisSeriesofLowOccupancyLED
CeilingMountedFixtures(IncludingStairwells)
Installation&OperationGuide
STAIRWELLX10FLOORX1
DIM
HILOW
POWER
HILOW
DIMSettingcontrols
thelightlevelwhenthe
stairwellisunoccupied.
POWERSetting
controlsthelight
levelwhenthe
stairwellisoccupied.
STAIRWELLX10FLOORX1
TEST
DIAG.STATUS