Unit installation

DCN: 141-00885-16 1/26/06 TZ40 Thermostat Manual 28
TZ40 ZWave Adapter
The TZ40 comes with an external ZWave adapter (ZWB) that connects to the TZ40 RS485 port. The
RS485 port is dedicated to the ZWave adapter and cannot be used for other communications.
NOTE: DO NOT CHANGE THE DEFAULT RS485 ADDRESS OF THE THERMOSTAT (SET TO 1).
The TZ40 supports the standard ZWave protocol for thermostats.
Connect the adapter as shown and proceed with enrolling the device into your ZWave network.
ZWB ZWave Thermostat Adapter Wiring
1. Place the ZWB in a convenient location that gets good ZWave reception. You must have access
to the ZWB module to set the ZWave network address.
2. Connect the ZWB to the TZ40 HVAC control unit with 22-24Ga wiring. (Category 3-5 wiring
acceptable). Wiring can be up to 1000ft.
3. Connect the D+, D- and Gnd terminals on the ZWB module to the RS485 connection on the TZ40
control unit.
4. Connect the 12V terminal on the ZWB to the 12V terminal on the WDU terminal on the TZ40
control unit.
5. Power up TZ40 HVAC control unit and observe that the ZWB Power LED is on.
6. Enroll the ZWave adapter in to the ZWave network using a ZWave network remote or other
control system interface.
7. Confirm ZWave message traffic with the Network LED.
TZ40
Control Unit
ZWBT-485
ZWave Thermostat
Adapter
RX/D-
TX/D+
12V
Gnd
Program
button
Power LED
Network
Data LED
WDU
12V
GND
D
C
J1
J2
RS485
GND
D -
D +