Unit installation

DCN: 141-00885-16 1/26/06 TZ40 Thermostat Manual 23
TZ40 Wall Display Unit Installation
WDU Location. Choose a location that best represents the temperature of the area to be controlled.
Avoid locations that are subject to drafts, from doors and windows, or areas with direct sunlight exposure.
WDU Mounting
Route the wires to the WDU through the access hole in the back of the case. Mount the WDU to the wall
with the screws and anchors provided. Be sure to plug any large access hole in the wall with sealer or
insulation to prevent wall drafts from affecting WDU operation.
WDU Prewiring
For new construction, the recommended wiring to the WDU from the Control Unit should be a two twisted
pair cable, 22 Ga minimum. Use of Category 5 wiring is preferred, but not required. In retrofit
applications the existing 18Ga thermostat wiring (a least 4 wires) is adequate and usually will work without
problems. However, such non-twisted wiring can be subject to interference due to adjacent in-wall high
voltage wiring.
Wiring the WDU to the Control Unit
Wiring the WDU is simply connecting the four wire cable from the Control Unit to the WDU terminal block.
Two wires are for data and two are for power. WDU power is 12VDC and provided by the Control Unit.
CAUTION: DO NOT MISWIRE THE POWER AND DATA LINES…DAMAGE WILL RESULT!!!
CHECK YOUR WIRING BEFORE APPLYING POWER…
Remote Sensor Connection
Model TS40 WDU has an remote sensor connector, J2, on the WDU base for connection of an external
remote temperature sensor. Follow the wiring diagram with the remote sensor to connect to the WDU.
-
+
C
D
1 GND
2 +12V
3 CLOCK
4 DATA
WIRING
ACCESS
HOLE
J1
TZ40 WDU WIRING DIAGRAM
TZ40 WDU
BASE
Hook TOP here and rotate into
base. Be sure pins engage in
connector correctly.
TO CLOSE
OPENING AND CLOSING THE WDU CASE
TO OPEN
PULL FROM LOWER CORNERS
CLOSE
BASE
For Remote Sensor
G
+5
C
D
J2