Unit installation
DCN: 141-00885-16 1/26/06 TZ40 Thermostat Manual 10
Main Menu > Schedules
The Schedules Screen allows you to review and set the setback schedule for the thermostat. The TZ40
has a 4 x 7 schedule. Four times a day can be selected for Heating and Cooling setpoints. Each day of
the week can have a different schedule. Groups of days can be copied with the same schedule. When
the TZ40 is set to “Run” mode, the schedule will be executed daily, with the setpoints being changed as
per that days schedule stored in the thermostat. “Hold” mode stops schedule operation and holds the
current setpoints until changed manually or by network commands.
The Schedules Screen gives you the option of setting a custom setback schedule or to load one of two
preset schedules.
Menu Options
• Heat and Cool: You can change the individual day/hour and setpoints for the Heating and
Cooling schedule by selecting this menu item.
• Preset: Comfort: This is a preset schedule with mild setbacks. Select this menu item to load
the Comfort schedule into the thermostat.
• Preset: EnergyMiser: This is a preset schedule with deeper setbacks. Select this menu item to
load the Energymiser schedule into the thermostat.
Schedules Screen
Screen navigation buttons:
Select Schedule
Heat and Cool
Preset: Comfort
Preset: EnergyMiser
Done
Select
Done
Select
Return to Main Menu Screen
Select the schedule to view or modify
Move menu selection pointer up
Move menu selection pointer down