System information

DCN: 141-01070-03 TR40 Thermostat Manual 18
Main Menu > User Settings > Sensor Calibration
The Sensor Calibration screen allows you to change the temperature calibration for the internal and any
external remote temperature sensors attached to the TR40 WDU. You can change the temperature
calibration by +/- 7 degrees.
When the Sensor Calibration screen is selected it will show the internal and all detected remote sensors.
Each sensor found will show the current temperature ((75) in the example screen below) and the current
number of degrees of offset being applied (1 deg in the example). N/a means that no remote sensor is
attached. If the sensor’s actual temp is (74) with 0 degrees of offset and you want it to be 75, then press +
to add 1 deg and it will show (75).
To change the temperature calibration, use the scroll buttons to select the internal or a remote sensor. Once
selected, use the + and buttons to change the temperature calibration to the desired setting.
The value shown in the (xx) is the calibrated or offset temperature that you want the sensor to show.
Sensor Calibration Screen
Sensor Calibration navigation buttons:
Sensor Calibration
Internal (75) 1
Remote 1 n/a 0
Remote 2 n/a 0
Remote 3 n/a 0
Done
+
Done
+
Return to Main Menu Screen
Increase the temperature by 1 deg
Decrease the temperature by 1 deg
Not used
Scroll Up
Scroll Down