Instruction manual
Fi d b b il & h B il M l
Fi
nne
d
 co
pp
er tu
b
e gas 
b
o
il
ers 
&
 water 
h
eaters – 
B
o
il
er 
M
anua
l
9
F
F
GENERAL VENTING GUIDELINES
   e vent installation must be in accordance with Part 
7, Venting of Equipment, of the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54-latest revision or 
applicable provisions of the local building codes. 
Canadian installations must comply with CSA B149.1 
or .2 Installation Code. Improper venting can result 
in excessive levels of carbon monoxide which can result 
in severe personal injury or death!
All vent systems must be fully supported by the building structure 
and not by the boiler/water heater. Appropriate thimbles and  re-
stops must be used where required.
  Common vent systems must be properly engineered 
and sized to provide a negative dra  of 0.01 to 0.08 
in, .25 to 2.0 mm WC at the  ue outlet! Common 
positive pressure vent systems are not to be used. 
Improper installation can result in excessive levels of 
carbon monoxide which can cause severe personal 
injury or death!
 A single acting barometric damper must be 
installed directly to the boiler/water heater  ue 
outlet to ensure proper operation.   is does not apply 
to outdoor units or direct vent positive pressure units.
  Some venting applications may require the stop to be 
removed for smooth operation.  e barometric 
damper should be located a er the  ue collector, refer 
to Figures 2, 7A and 8 for proper location. Be sure that 
the damper is mounted horizontally (never vertically). 
Carefully follow the instructions provided with the 
barometric damper. Check with local codes for speci c 
requirements.
  In Canada, B149 (7.25 Dra Regulators) states the 
damper shall be of double-acting type.
  To avoid spillage into the room of dangerous  ue gas 
containing carbon monoxide, the opening in damper 
must never face against the  ow of  ue gas.
VENT SYSTEM OPTIONS 
  e LCD may be vented the following ways:
1) Vertical/Chimney Venting, Negative Pressure, Category 
I - uses an approved metal chimney system or properly lined 
masonry chimney. Combustion air is obtained from the space 
in which the unit is installed or from outdoors. A barometric 
damper must be installed near the  ue outlet when venting 
vertically. See Figures 6 and 7.   is also applies to any fan-assisted 
chimneys or vents.
2)  Direct Vent, Positive Pressure, Category III - for 
horizontal vent runs equivalent to 35  ,  10.8 m or less. 
A stainless steel vent system certi ed to UL 1738 for 
installations in the United States. ULC S636 for 
installations in Canada must be used when combustion air is 
ducted from outdoors, from the same wall.
3)  Horizontal Vent, Negative Pressure, Category I -
for horizontal vent runs equivalent to more than 35  ,
10.8 m (90° elbow equals 10 equivalent  ). A dedicated wall 
mounted power venter must be used.  e vent system can be 
single wall galvanized steel or type B vent pipe. Combustion 
air is obtained from the space in which the unit is installed or 
from the outdoors.
  A barometric damper must be installed when the horzontal run 
is longer than 35 equivalent feet. (90° elbow = 10 equivalent 
 ). If this is the case, a power venter must also be used.
  If horizontal run is less than 35 equivalent  , do not use a 
barometric damper. Follow applicable instructions under the 
“COMBUSTION AIR & VENTILATION” section.
4)  Outdoor Installation - uses the outdoor option kit. Barometric 
damper is not required.
 All venting, combusiton air material supplied by 
installer. All venting material must be approved for the 
application. Consult the vent manufacturer’s product 
literature










