COMBUSTION/SAFETY REPORT
FACTORY FIRE TEST REPORT:  Low Fire  High Fire
Manifold Gas Pressure: "WC" 
Air Differential Pressure: "WC"
FIELD TEST REPORT IN STAGE:  1  2  3  4
Manifold Gas Pressure: "WC" 
Air Differential Pressure: "WC"
Pilot Manifold Pressure: "WC"    
CO
2
:
Stack Temp. (Net):
Effi ciency @   °F Inlet Temp.
CO (PPM):
O
2
:
Stack Draft (Must Be Negative):
Pilot Signal:
SAFETY CONTROL CHECK:
Low Water Cut Off (PPM):
Factory Flow Switch
Operating Control
High Limit
Differential Air Switch STG. 1, 2
Differential Air Switch STG. 3, 4
Blocked Flu Switch
Flame Failure Lockout (CSD-1)
Pump Delay
Combustion Air Damper
Power Vent Proving Switch
Barometric Damper 
COMMISSIONING THE UNIT
Customer Instructed?  Yes  No 
All Covers Replaced?  Yes  No
Wiring Secure/Tight?  Yes  No
Customer Given Manual?  Yes  No
Cabinet Air Leaks?  Yes  No 
Gas Leaks Detected?  Yes  No 
Unit Cycled Min. of 15 X?  Yes  No
Temp. Set Per Customer?  Yes  No 
Left Maintenance Instruction?  Yes  No
Commissioned By: 
(Signature)
Date:
The delta T between the heaters inlet and outlet 
is critical to proper fl ow. Before you leave the 
job site you must record the delta T. This reading 
should not exceed 35°F, 19.4°C or be lower than 
20°F, 11.1°C.
 Inlet Temperature
 Outlet Temperature
Wired and Operating 
Properly @ Setting:
Failed To Operate 
Comment To Right Comments
These results are affi xed 
to the side of the heater 
on a small white label.