Instruction manual
Fi d b b il & h B il M l
Fi
nne
d
co
pp
er tu
b
e gas
b
o
il
ers
&
water
h
eaters –
B
o
il
er
M
anua
l
23
F
F
BOILER/WATER HEATER OPERATION
Staging Operation
e LCD boiler/water heater series is separated into on/o and
2-stage units depending on the model selected. e 225-400 models
have on/o staging, while the 600 through 2300 models have a
two stage option. Input staging is controlled from an aquastat
controller that signals the relays to select the blower and gas valve
modes. Per DOE mandate, the (LB225/300) operator control
incorporates an automatic means (outdoor reset) of adjusting the
boiler water temperature for hot water heating. e boiler will not
operate without the outdoor sensor installed. Table 13 identi es
the stages and ring modes associated with the standard single stage
units. Table 14 identi es the stages and ring modes associated
with the two stage option.
Table 13 Firing modes (L225-L2300)
Stage Firing Mode
O O
1On
Table 14 Firing modes (L600-L2300)
Stage Firing Mode
O O
1Low Fire
2 High Fire
e outlet water temperature is automatically controlled by the
aquastat. e optional staging function is controlled by a return
water aquastat. e return water aquastat utilizes inputs from the
inlet water temperature sensors or optional tank sensors to stage
the boiler/water heater as required.
Pressure Switch Settings
Di erential pressure switches are provided in the LCD to shut down
gas ow under a blocked ue or inlet condition. A single pressure
switch is used on the standard models. One low re and one high
re pressure switch is used when the two-stage option is employed.
e low re pressure switch serves to shut down gas ow if there
is a blocked ue or inlet condition during low re operation. Similarly,
the high re switches will shut down gas ow if there is a blocked
ue or inlet condition during high re operation. e di erential
pressure is taken between the air plenum and the pressure
inside one of the main burners.
Pressure taps are provided in the control compartment for taking
the di erential pressure readings, Figure 17. Table 15 lists the
di erential pressure se ings for all of the models.
Figure 17 Pressure switch tap(s)
Table 15 Differential pressure settings (all units)
Model
Di erential Pressure
Requirement at High Fire
(All Units)
Inches WC mm WC
225-300 1.0 ± 1.1 25.4 ± 27.9
400 0.7 ± 0.8 17.8 ± 20.3
600-2300 1.0 ± 1.1 25.4 ± 27.9
On all units, the pressure switch(es) will interrupt power to the
control module under a blocked ue or inlet condition. is will
cause the pilot and main gas valves to close. Tables 16 and 17 identify
how pressure switch control changes during boiler/water heater
staging. Tables 18 and 19 identify the control actions if a low air
condition occurs at any stage.
Table 16 Pressure switch control, L225-L400
Stage Pressure Switch Mode
O O
1 High Fire
Table 17 Pressure switch control, L600-L2300
Stage Pressure Switch Mode
O O
1Low Fire
2 High Fire