BOILER/WATER HEATER OPERATION
Staging Operation
 e LCD boiler/water heater series is separated into on/o and 
2-stage units depending on the model selected.   e 225-400 models 
have on/o staging, while the 600 through 2300 models have a 
two stage option. Input staging is controlled from an aquastat 
controller that signals the relays to select the blower and gas valve 
modes. Per DOE mandate, the (LB225/300) operator control 
incorporates an automatic means (outdoor reset) of adjusting the 
boiler water temperature for hot water heating.   e boiler will not 
operate without the outdoor sensor installed. Table 13 identi es 
the stages and  ring modes associated with the standard single stage 
units. Table 14 identi es the stages and  ring modes associated 
with the two stage option.
Table 13  Firing modes (L225-L2300)
Stage Firing Mode
O O 
1On
Table 14  Firing modes (L600-L2300)
Stage Firing Mode
O O 
1Low Fire
2 High Fire
  e outlet water temperature is automatically controlled by the 
aquastat.   e optional staging function is controlled by a return 
water aquastat.  e return water aquastat utilizes inputs from the 
inlet water temperature sensors or optional tank sensors to stage 
the boiler/water heater as required. 
Pressure Switch Settings
Di erential pressure switches are provided in the LCD to shut down 
gas  ow under a blocked  ue or inlet condition. A single pressure 
switch is used on the standard models. One low  re and one high 
 re pressure switch is used when the two-stage option is employed. 
 e low  re pressure switch serves to shut down gas  ow if there 
is a blocked  ue or inlet condition during low  re operation. Similarly, 
the high  re switches will shut down gas  ow if there is a blocked 
 ue or inlet condition during high  re operation.  e di erential 
pressure is taken between the air plenum and the pressure 
inside one of the main burners.
Pressure taps are provided in the control compartment for taking 
the di erential pressure readings, Figure 17. Table 15 lists the 
di erential pressure se ings for all of the models.
Figure 17  Pressure switch tap(s)
Table 15  Differential pressure settings (all units)
Model 
Di erential Pressure 
Requirement at High Fire
(All Units)
Inches WC mm WC
225-300 1.0 ± 1.1 25.4 ± 27.9
400 0.7 ± 0.8 17.8 ± 20.3
600-2300 1.0 ± 1.1 25.4 ± 27.9
On all units, the pressure switch(es) will interrupt power to the 
control module under a blocked  ue or inlet condition.  is will 
cause the pilot and main gas valves to close. Tables 16 and 17 identify 
how pressure switch control changes during boiler/water heater 
staging. Tables 18 and 19 identify the control actions if a low air 
condition occurs at any stage.
Table 16  Pressure switch control, L225-L400 
Stage Pressure Switch Mode
O O 
1 High Fire
Table 17  Pressure switch control, L600-L2300
Stage Pressure Switch Mode
O O 
1Low Fire
2 High Fire