Instruction manual
Fi d b b il & h B il M l
Fi
nne
d
 co
pp
er tu
b
e gas 
b
o
il
ers 
&
 water 
h
eaters – 
B
o
il
er 
M
anua
l
18
F
F
DOMESTIC WATER SUPPLY PIPING
  Proper control se ings must be used to prevent water 
supplied for domestic use from exceeding 130°F, 54°C 
or a scald injury will occur! When higher water 
temperatures are required for appliances such as a 
dishwasher, a mixing valve or some other tempering 
means must be installed. Households with small 
children may require water temperatures less than 
120°F, 49°C. Local codes must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze headers. Piping 
and components connected to the water heater must be suitable for 
use with potable water.  e water heater must not be connected to 
any heating system piping or components previously used with a 
non-potable water heating appliance. No toxic chemicals, such as those 
used for boiler treatment, are to be introduced into the potable water 
used for space heating. If a hot water storage tank is used in the system 
it must be equipped with a temperature and pressure relief valve 
that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.
   e storage tank must be located as close to the water 
heater as possible to prevent excessive head loss which 
will reduce  ow.
Water Chemistry
 e required temperature rise across the water heater is based on 
water having a hardness between 8 and 18 grains per gallon with 
a level of dissolved solids not exceeding 350 ppm. Water having a 
hardness less than 8 grains can cause excessive errosion of the heat 
exchanger. Water that has a hardness greater than 18 grains per 
gallon and/or a level of dissolved solids exceeding 350 ppm will 
require a recalculation of the pump size and temperature rise. 
A cupro-nickel heat exchanger may also be required. The 
manufacturer should be consulted when these water conditions are 
encountered. See Table 9A
  e maximum allowable  ow rate through a LCD water 
heater with copper heat exchanger is 92 GPM, 5.8 L/s 
on 225 1200 models and 115 GPM, 7.3 L/s on 1480 to 
2300 models.   e cupro-nickel heat exchanger allows for 
100 GPM, 6.3 L/s on 225 to 1200 models 125 GPM, 
7.9 L/s on 1480 to 2300 models, see Table 9B .
RBI water heaters are designed to run scale free. Due to the extreme 
variables of water conditions world wide it is necessary to consider 
pH values and water hardness in relationship to scaling. It is crucial 
to consider these two variables when making heat exchanger and 
pump selection. If local water conditions are extreme follow the 
guidelines in the Heat Exchanger Selection Table (Table 9A) and the 
Pumping Performance Table (Table 9B). Scale free operation can be 
achieved by using water with a hardness between 8 and 18 and by 
maintaining the pH between 5 and 9. Follow the conditions listed 
under NORMAL in the table. In some areas of the country additional 
precautions must be observed due to unusual characteristics of the 
local water supply. Call the nearest RBI representative for details.
To properly size the pump a grain hardness and pH test must be taken 
at the installation site before the order is placed. Proper pump sizing 
will improve heater performance and help ensure heater longevity.
Expansion Tank
An expansion tank or other means to control thermal expansion 
must be installed in the water heating system if back  ow prevention 
devices are installed.
Cold Water Supply
 e cold water supply must be piped to the water heater’s outlet 
piping between the water heater and the hot water storage tank. 
  is will prevent untempered water from entering the water heater, 
see the Temperature Rise Control section below. A typical water 
heating system is shown in Figure 14 and 15.
Pump Requirements
  is low-mass water heater requires a continuous minimum water 
 ow for proper operation.   e low water  ow switch provided for 
this unit will shut down the water heater if  ow falls below the 
required minimum level. Table 9B provides the heat exchanger 
pressure drop chart and temperature rise table.  e temperature 
rise across the water heater must never exceed 35°F, 19.4°C.
Temperature Rise Control
Water returned to the water heater inlet must not be less than 125°F, 
52°C or excessive condensation of the products of combustion will 
damage the water heater voiding the warranty.   e method outlined 
below can be employed to prevent this condition from occurring. 
A balancing valve should be installed on the outlet side of the water 
heater for purposes of adjusting the  ow rate through the heat 
exchanger.   ermometers are installed on both the inlet and outlet 
of the water heater for determining the temperature rise through the 
unit.   e proper velocity through the water heater must be maintained 
in accordance with Table 9B for e  cient operation and long life. 
If the temperature rise through the water heater is lower than 
recommended the water velocity is too high. Premature erosion of 
the heat exchanger will occur. Conversely, if the temperature rise is 
higher than recommended in Table 9B the  ow rate is too low. Scaling 
and so ening of the heat exchanger will occur.
Thermostatic Mixing Valve - 
Water Above 140°F, 60°C
Water can be stored at temperatures above 140°F, 60°C provided 
that a thermostatically controlled mixing valve is used to temper 
the hot water to an acceptable temperature before it’s supplied for 
domestic use.
  e mixing valve MUST be set to prevent a scald injury from 
occurring, see the caution against scalding above. 
Storage of water for domestic use above 140°F, 60°C will provide 
an increased quantity of tempered water and help prevent growth 
of water born bacteria. 










