Operating instructions
19
The discharge opening must be a minimum of 2 ft ver-
tically from the roof surface and at least 2 ft higher than
any part of the building within 10 ft.  Vent stack shall be
at least 5 ft in vertical height above the drafthood out-
let. The vent cap location shall have a minimum clear-
ance  of 4  ft  horizontally  from,  and in no  case  below,
unless  a  4  ft  horizontal  distance  is  maintained,  from
electric  meters,  gas  meters,  regulators  and  relief
e
quipment.
The weight of the vent stack or chimney must not rest
on  heater  drafthood.  Support  must  be provided  in
compliance with applicable codes.  The heater top and
drafthood must be readily removable for maintenance
and inspection.  Vent pipe should be adequately sup-
ported to maintain proper clearances from combustible
construction.
Type "B" double-wall or equivalent vent pipe is recom-
mended. However single-wall metal vent pipe may be
used as specified in  the latest edition of the  National
Flue  Gas  Code  ANSI  Z223.1  (Canada  -  CAN/CSA-
B149).
GAS SUPPLY CONNECTIONS
Gas  piping  must  have  a  sediment  trap  ahead  of  the
heater gas controls, and a manual shut-off valve locat-
ed outside the heater jacket.  All gas piping should be
tested after installation in accordance with local codes.
CAUTION: The heater and its manual shut-off valve
must be disconnected from the gas supply during any
pressure  testing  of  that  system  at  test  pressures  in
excess of 1/2 psi (3.45 kPa).  Dissipate test pressure
in the gas supply line before reconnecting the heater
and its manual shut off valve to gas supply line.  FAIL-
URE  TO  FOLLOW  THIS  PROCEDURE  MAY  DAM-
AGE THE GAS VALVE. OVER PRESSURIZED GAS
VALVES ARE NOT COVERED BY WARRANTY.  The
heater  and  its  gas  connections  shall  be  leak  tested
before placing the appliance in operation. Use soapy
water for leak test.  DO NOT use open flame.
5' MIN
2' MIN
10' OR LESS
2' MIN
VENT CAP
VENT PIPE
DRAFT HOOD
HEATER
NOTE: Do not use Teflon tape on gas line pipe thread.
A  pipe  compound  rated  for  use  with  natural  and
propane gases is recommended. Apply sparingly only
on male pipe ends, leaving the two end threads bare.
A minimum of 7 in. WC and a maximum of 14 in. WC
upstream pressure under load, and no-load conditions
must  be  provided  for natural  gas or  a minimum  of
12 in. WC and a maximum of 14 in. WC for propane
gas.
SUPPLY PRESSURES
NOTE: With  venting  application  of  two  or  more
heaters, contact the factory.










