Specifications
TM022 Raypak RHP 33 Pool and Spa Heat Pump Service Instructions REV C
D.O.I: 14/03/2006
33
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
4. Disconnect black wire from terminal 1 of fan relay and push through control panel
grommet.
5. Cut cable ties holding fan wiring to back of control panel.
6. Remove 9 screws around top cover and lift out whole top cover assembly including fan
and grill.
7. Reassemble in reverse order of above.
Transformer: (Procedure 4)
Personal Protective Equipment should be worn when conducting step 2 of
this procedure to reduce the risk of electric shock. Refer to Rheem Safety
Procedure on electrical testing.
1. Remove control panel cover (see procedure 1).
2. Confirm with a multi-meter between Active and Neutral at the Compressor
contactor Line terminals that voltage is not present.
3. Disconnect wiring from transformer paying attention to where each wire is connected.
4. Remove two tapped screws on transformer base and remove transformer.
5. Reassemble in reverse order of above.
High Pressure Switch: (Procedure 5)
Personal Protective Equipment should be worn when conducting step 2 of
this procedure to reduce the risk of electric shock. Refer to Rheem Safety
Procedure on electrical testing.
The fan motor may commence operation without warning. Failure to isolate
the power may result in serious injury if the fan commences operation.
Personnel qualified and licensed to work with refrigerants may only carry
out the following repair procedures to the sealed refrigeration system.
The following procedures assume that all work conducted conforms to the
refrigeration code of good practice. During repair the R22 refrigerant must
be recovered, not vented to atmosphere.
1. Remove control panel cover and access panel (see procedures 1 & 2).
2. Confirm with a multi-meter between Active and Neutral at the Compressor
contactor Line terminals that voltage is not present.
3. Recover refrigerant charge.
4. Cut cable ties and disconnect pressure switch wiring from terminals 1 and 9 of the
terminal block pulling wires through control panel grommet.
5. Unscrew and remove high pressure switch from refrigeration pipe.
6. Reassemble in reverse order of above.
7. Recharge system with R22. Refer to “refrigerant charge” on page 11.
Low Pressure Switch: (Procedure 6)
Personal Protective Equipment should be worn when conducting step 2 of
this procedure to reduce the risk of electric shock. Refer to Rheem Safety
Procedure on electrical testing.
The fan motor may commence operation without warning. Failure to isolate
the power may result in serious injury if the fan commences operation.