Specifications
TM022 Raypak RHP 33 Pool and Spa Heat Pump Service Instructions REV C
D.O.I: 14/03/2006
27
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
Component Tests 11 - 14
Test 11 Test 12
Warning – ‘Live’ equipment Personal
Protective Equipment should be worn
when conducting this test.
Using a multimeter on the AC voltage
scale, measure across terminals E6 &
E11 on the control board. Normal voltage
is 24 volts.
Warning – ‘Live’ equipment Personal
Protective Equipment should be worn
when conducting this test.
Using a multimeter on the AC voltage scale,
measure across terminal 1 on the fan relay
and Line 2 on the compressor contactor.
Normal voltage is 240 volts.
Note: Control board must be calling for heat
for this test.
Test 13 Test 14
Ensure power is isolated before
conducting test
Using a multimeter set on the resistance
scale, measure across the black wire on
terminal 1 of the fan relay and the purple
wire on the capacitor (run winding), and
across the black wire on terminal 1 of the
fan relay and the brown wire on the
capacitor (start winding).
Normal resistance for the run winding is
19 ohms. Normal resistance for the start
winding is 44.2 ohms when the fan is
cold.
Ensure power is isolated before
conducting test
Disconnect the wiring to the capacitor and
using a multimeter set on the capacitance
(µf) scale measure across the capacitor
terminals.
Black to white terminals (compressor)
Normal capacitance is 50 µf
Black to green terminals (fan)
Normal capacitance is 5 µf