500-RPK Raypak B6000 Metasys™ N2 System Protocol Interface Raypak Burner Controller User Manual March 15, 2005
Please Read This Notice Successful application of this module requires a reasonable working knowledge of the Raypak B6000 Metasys™ N2 System Protocol Interface Raypak Burner Controller hardware and the application in which the combination is to be used. For this reason, it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions.
Contents 1500-RPK ♦ Raypak Burner Controller Contents PLEASE READ THIS NOTICE...........................................................................................................2 Your Feedback Please ..................................................................................................................2 1 2 PRODUCT SPECIFICATIONS....................................................................................................5 1.1 Metasys N2 Slave Interface..........................
1500-RPK ♦ Raypak Burner Controller 5 Contents 4.2 Control Commands ...................................................................................................... 16 4.3 Device Identifier Code.................................................................................................. 16 DIAGNOSTICS ......................................................................................................................... 17 5.1 LED Indicators ..............................................
Product Specifications 1 1500-RPK ♦ Raypak Burner Controller Product Specifications In This Chapter ¾ Metasys N2 Slave Interface ..................................................... 5 ¾ Raypak B6000 Interface........................................................... 6 ¾ General Specifications ............................................................. 6 ¾ Hardware Specifications .......................................................... 6 The ProSoft Technology, Inc.
1500-RPK ♦ Raypak Burner Controller F : Product Specifications Identify Device Type The following commands are recognized, and acknowledged, but do not have impact on the operation of the 1500-N2, and do not return any data: 0/0 : Time Update 0/8 : Warm Start All other commands return a Bad Command Error Code 1.2 1.
Metasys Slave Port Functionality 2 1500-RPK ♦ Raypak Burner Controller Metasys Slave Port Functionality In This Chapter 2.1 ¾ N2 Slave Communications ....................................................... 7 ¾ N2 Point Layout........................................................................ 9 N2 Slave Communications The ProSoft 1500 card supports the Johnson Controls Metasys™ N2 Protocol, as a slave, on port 1.
1500-RPK ♦ Raypak Burner Controller Metasys Slave Port Functionality Data Types The N2 System protocol treats data as objects, with each data type having a different structure and purpose. The data types recognized by the 1500 card are as follows: Binary Input Binary Output Analog Input Analog Output Reading Attributes The data objects contain attributes which describe several a data point, and some of its functionality.
Metasys Slave Port Functionality 1500-RPK ♦ Raypak Burner Controller Status Update The host can issue a 'Status Update' command to the 1500. The response will contain device information ("1500-N2 Rev 1.0A") as well as current status information. 0/9 Status Update Identify Device When a master host first powers up, the 'Identify Device' command is issued to all of the slaves. In the case of the 1500 card, the Device Code 10 Hex is returned to the host.
1500-RPK ♦ Raypak Burner Controller Page 10 of 32 Metasys Slave Port Functionality ProSoft Technology, Inc.
Hardware Setup 3 1500-RPK ♦ Raypak Burner Controller Hardware Setup In This Chapter 3.1 ¾ 1500 Card Setup .................................................................... 11 ¾ B6000 Communications ......................................................... 13 1500 Card Setup 3.1.1 Connecting Power to the 1500 Card The 1500 Card requires an external source of DC voltage. The DC source voltage should be between 9V and 30V.
1500-RPK ♦ Raypak Burner Controller Hardware Setup SW 2 : Metasys N2 Slave Address Switch Function Position 1 Address Bit 0| Value = 1 Example: 2 Address Bit 1| Value = 2 Address 12 3 Address Bit 2| Value = 4 Bits 8 7 6 5 4 3 2 1 4 Address Bit 3 | Value = 8 00001100 5 Address Bit 4| Value = 16 6 Address Bit 5| Value = 32 7 Address Bit 6| Value = 64 8 Address Bit 7| Value = 128 The parameters are defined as follows: Metasys N2 Slave Address: Each of the separate drops off of a Johnso
Hardware Setup 3.2 1500-RPK ♦ Raypak Burner Controller B6000 Communications The B6000 communications interface has been hard coded to operate at the following default conditions: Baud 9600 Parity Odd Stop Bits 1 The 1500 card emulates the modem card that is regularly connected to the B6000 Controller. This is important as when the 1500 card is connected to the B6000, the modem card cannot be connected simultaneously. Default Baud Rates and Parity for all supported devices are different.
1500-RPK ♦ Raypak Burner Controller Page 14 of 32 Hardware Setup ProSoft Technology, Inc.
N2 System Protocol Support 4 1500-RPK ♦ Raypak Burner Controller N2 System Protocol Support In This Chapter ¾ Attribute Commands .............................................................. 15 ¾ Control Commands ................................................................ 16 ¾ Device Identifier Code............................................................ 16 The ProSoft Technology 1500 card supports several data read and write commands for the N2 System protocol.
1500-RPK ♦ Raypak Burner Controller 4.1.3 N2 System Protocol Support Analog Output The Analog Output data object is used by the 1500 as a simple conduit for setpoints in the B6000. No support is provided for scaling the output value, or for verifying the saturation level of the output value. The value written from the master is communicated to the Controller. 4.1.4 Binary Output The Binary Output data object is implemented to respond directly to the commands received from the master.
Diagnostics 5 1500-RPK ♦ Raypak Burner Controller Diagnostics In This Chapter ¾ LED Indicators........................................................................ 17 Several hardware diagnostics capabilities have been implemented using the LED indicator lights on the front of the 1500 card. The possible conditions as indicated by the lights are: 5.1 LED Indicators Several hardware diagnostics capabilities have been implemented using the LED indicator lights on the front of the module.
1500-RPK ♦ Raypak Burner Controller Page 18 of 32 Diagnostics ProSoft Technology, Inc.
APPENDIX A - Metasys Point Mapping 1500-RPK ♦ Raypak Burner Controller APPENDIX A - Metasys Point Mapping In This Chapter ¾ Raypak Metasys Register Assignements............................... 19 ¾ Raypak Metasys Register Assignements............................... 20 Raypak Metasys Register Assignements Analog Output Parm Offset Description AO1 28 Setpoint Day Setup (Desired water temp @ 70F) AO2 29 Niteset Night Setpoint (Desired water temp @ 70F) 2 AO3 30 Ratio Out 1-200 = 0.1 – 20.
1500-RPK ♦ Raypak Burner Controller APPENDIX A - Metasys Point Mapping Analog Output Parm Offset Description AO28 55 Time – Min 28 AO29 56 Time – DWK 29 AO30 57 Lead Change Hours 30 58 Night Setback Binary Output Parm Offset Description BI_1 0 Bit 0 = Night Setback present 59 Controller LED Status BI_2 0 Bit 0 = Fault Status (1=system fault) BI_3 1 Bit 1 = Call Out Request ( 1 = Yes) Msg #2 1 2 Raypak Metasys Register Assignements Analog Input Parm Offset Description A
APPENDIX A - Metasys Point Mapping 1500-RPK ♦ Raypak Burner Controller Analog Input Parm Offset Description AI_12 79 Setpoint Day Setup (Desired water temp) 9 AI_13 80 Niteset Night Setpoint (Desired water temp) 10 AI_14 81 Ratio Out 1-200 = 0.1 - 20.0 in 0.1 incr.
1500-RPK ♦ Raypak Burner Controller APPENDIX A - Metasys Point Mapping Analog Input Parm Offset Description AI_49 123/124 Boiler Valve Up Times (Sec) #7 AI_50 125/126 Boiler Valve Up Times (Sec) #8 AI_51 127/128 Boiler Valve Down Times (Sec) #1 AI_52 129/130 Boiler Valve Down Times (Sec) #2 AI_53 131/132 Boiler Valve Down Times (Sec) #3 AI_54 133/134 Boiler Valve Down Times (Sec) #4 AI_55 135/136 Boiler Valve Down Times (Sec) #5 AI_56 137/138 Boiler Valve Down Times (Sec)
APPENDIX A - Metasys Point Mapping 1500-RPK ♦ Raypak Burner Controller Analog Input Parm Offset Description AO36 165 KDD: Diff Constant Denominator (0-255) Binary Input Parm Offset Description BO_1 166 Initialize B6000 by writing STAR 80h 0dh to unit STAR BO_2 167 Setback on/off control (0 = Off, 1 = On) Write word value to B6000 4025h 168 Spare 169 Spare ProSoft Technology, Inc.
1500-RPK ♦ Raypak Burner Controller Page 24 of 32 APPENDIX A - Metasys Point Mapping ProSoft Technology, Inc.
APPENDIX B - Communication Cable Connection Diagrams1500-RPK ♦ Raypak Burner Controller APPENDIX B - Communication Cable Connection Diagrams In This Chapter ¾ PORT 1 - N2 System Protocol Slave Communication Port .... 25 ¾ PORT 2 - Raypak B6000 Controller Communication Port......
1500-RPK ♦ Raypak Burner ControllerAPPENDIX B - Communication Cable Connection Diagrams Page 26 of 32 ProSoft Technology, Inc.
Support, Service & Warranty 1500-RPK ♦ Raypak Burner Controller Support, Service & Warranty ProSoft Technology, Inc. survives on its ability to provide meaningful support to its customers. Should any questions or problems arise, please feel free to contact us at: Internet Web Site: http://www.prosoft-technology.com/support E-mail address: support@prosoft-technology.com Phone (661) 716-5100 (661) 716-5101 (Fax) Postal Mail ProSoft Technology, Inc.
1500-RPK ♦ Raypak Burner Controller Support, Service & Warranty General Warranty Policy ProSoft Technology, Inc. (Hereinafter referred to as ProSoft) warrants that the Product shall conform to and perform in accordance with published technical specifications and the accompanying written materials, and shall be free of defects in materials and workmanship, for the period of time herein indicated, such warranty period commencing upon receipt of the Product.
Support, Service & Warranty 1500-RPK ♦ Raypak Burner Controller Hardware Product Warranty Details Warranty Period: ProSoft warranties hardware Product for a period of 1 year. Warranty Procedure: Upon return of the hardware Product ProSoft will, at its option, repair or replace Product at no additional charge, freight prepaid, except as set forth below. Repair parts and replacement Product will be furnished on an exchange basis and will be either reconditioned or new.
1500-RPK ♦ Raypak Burner Controller Page 30 of 32 Support, Service & Warranty ProSoft Technology, Inc.
Index 1500-RPK ♦ Raypak B6000 Metasys™ N2 System Protocol Interface Raypak Burner Controller Hardware Setup • 11 Hardware Specifications • 6 Index I Identify Device • 9 ( (02) Read Input Status • 15 1 1500 Card Setup • 11 1500 Jumper Configurations • 12 A Analog Input • 15 Analog Output • 16 APPENDIX A - Metasys Point Mapping • 9, 19 APPENDIX B - Communication Cable Connection Diagrams • 25 Attribute Commands • 15 B B6000 Communications • 13 Binary Input • 15 Binary Output • 16 C Command Error Chec