Specifications

TM018 Raypak 131 Type A Pool & Spa Heaters REV: A
D.O.I: 8/04/2009
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
39
Fault Finding Tests 16 19
Test 16
Test 17
Using a multimeter on the AC voltage
scale, measure between the brown wire
terminal and the blue wire terminal on relay
1.
The following result should be obtained:
24 Volts AC.
Disconnect wiring at 55ºC outlet high limit
and using a multimeter on the ohms scale,
measure between the two terminals on the
55ºC outlet high limit.
The following result should be obtained:
0 ohms (high limit contact closed).
Test 18
Test 19
Using a multimeter on the AC voltage
scale, measure between each purple wire
and the blue wire on the RAM ignition
module terminal strip.
The following results should be obtained:
1
st
purple wire blue wire: 24 Volts AC.
2
nd
purple wire blue wire: 24 Volts AC.
Using a multimeter on the AC voltage
scale, measure between the brown wire
and the blue wire on the RAM ignition
module terminal strip.
The following result should be obtained:
24 Volts AC.