Brochure
T
}
}
}
}
PC Board and Electrical Hook Up
Model 0014 Cartridge Circulator
Model Nomenclature
  F – Cast Iron, Flanged
  BF – Bronze, Flanged
Variations:
  Z  – Zoning Circulator
   J – Bronze Cartridge with Cast Iron Casing
F
G
C
B
A
D
  Model     Volts-   Hz    Ph    Amps    RPM     HP
  0014-F1     115    60      1     1.55      3250     1/8
  0014-BF1    115    60      1     1.55      3250     1/8
  Motor     Permanent Split Capacitor 
  Type      Impedance Protected
Motor 
 Options 
220/50/1, 220/60/1,  230/60/1,  100/110/50/60/1
Electrical Data
Performance Data 
  Flow Range:  0 – 32 GPM
  Head Range:  0 – 22 Feet
  Connection Sizes:  3/4", 1", 1-1/4", 1-1/2" Flanged
Application
The  Taco  0014  is  specifically  designed  for  medium  head  /  medium  flow  applications  in  Large  
Residential/Light  Commercial  systems.    Ideal  for  large  BTUH  Boilers,  Primary/Secondary  loops, 
Commercial Water Heaters, and light Commercial Heating and Cooling systems.  The Bronze 0014 
should be used on open loop systems.  The unique replaceable cartridge contains all of the moving 
parts and allows for easy service instead of replacing the entire circulator. Universal flange to flange 
dimensions and orientation allows the 0014 to easily replace other models.  The Compact, Direct-
Drive, Low Power Consumption design makes it ideal for high-efficiency jobs.  
Pump Dimensions & Weights
     A  B  C  D  F  G  Ship Wt.
 Model  Casing  in.  mm  in.  mm  in.  mm  in.  mm  in.  mm  in.  mm  lbs.  Kg
 0014-F1  Cast Iron  7-1/4  184  5-13/16  148  3-1/4  83  3-5/16  84  5-3/8  137  6-1/2  165  12.0  5.5
 0014-BF1   Bronze  7-1/4  184  5-13/16  148  3-1/4  83  3-5/16  84  5-3/8  137  6-1/2  165  12.0  5.5
Application
Thermostat ready.  The Taco Priority Zoning Circulator combines the reliability of the “00
®
” circulator with the 
convenience and efficiency of a PC board mounted switching relay package.  Each zoning circulator has low and 
high voltage terminal strips for ease of electrical hookup, as well as a built-in priority switch.  The priority switch 
allows the installer to choose the zone that requires the most attention and, when activated, run only that circula-
tor. The priority zoning circulator can be used in conjunction with other circulators or zone valves. It is ideal for 
indirect hot water heaters, adding another zone, zoning with circulators, and for prioritizing under-sized zones.  
Available in a full range of sizes from 003 - 0014.
Model 007 Cartridge CirculatorPriority Zoning Circulator
Features
  “00
®
” Reliability 
  Snap-in PC Board 
  Low and High Voltage Terminal Strips
  UL and CSA Listed
  Simplified Wiring
  LED Power Light
  100% Factory Tested
  Works With Other Circulators 
  or Zone Valves
  Universal Thermostat Compatibility
  Available In Sizes 003 - 0014
  Patented Design
  Made in the USA
Contact Ratings 
  Terminals 1 & 2  24VAC  1 Phase
  Terminals 3 & 4  24VAC  1 Phase 5 Amps
          115VAC  1 Phase 5 Amps
                   240VAC    1 Phase 5 Amps (max)
  PR-IN & PR-OUT  115VAC   1 Phase 8 Amps
            Inrush Current 
(max)
  Live & Neutral    115VAC  1 Phase
 (max)
Thermostat Ratings
  24VAC SPDT 2-Wire Heating
  24VAC Digital Electronic
  2-Wire Max Draw 30 Milliamps
115 VAC Power
24 VAC Control 
Room Thermostat 
AquaStat
Dry Contact: 
Terminals 3 & 4  
24 VAC, 115 VAC or 
240 VACT-T Boiler
Priority In-Out  
(115 VAC)
Removable PC Board
F
G
C
B
A
D