Specifications
SEE FIG. 14
After 15 minutes of the burner running.
To sample the flue gases from the cooker burner lift up
the R.H. insulating cover and remove the countersunk
headed screw and insert the sensing end of a portable
analyser to check the CO
2
(Carbon Dioxide) level in the
hotplate. The cooker burner should be set to 11.0% CO
2
.
IMPORTANT:
Ensure that the bottom louvered plinth is in place during
combustion setting procedures and the outer door is
closed.
Remove the CO
2
sampling tube and using the same hole
for flue sampling insert the sensing end of a Baccarach
Smoke Pump and check that the smoke in the flue ways
does not exceed 0-1 on the scale.
Replace the countersunk headed screw on completion
ensuring that it will not interfere with any pots and pans
placed on the hotplate.
12
SET COMBUSTION AIR
CHECK SMOKE
Re-commissioning - Oil
FIG. 14 DESN 514111