RAYBURN 370 SFW To ensure safety, satisfaction and maximum service, this Cooker should be installed by a suitably qualified and competent person. The provision of a Central Heating facility, requires that the hot water systems involved, conform fully to good plumbing practice and established standards.
TABLE OF CONTENTS Page No. 1. 2. Technical Data .................................................................................................................................. 3 Specification ......................................................................................................................................4 3. Site Preparation .................................................................................................................................5 4. Cooker Position.......
Consumer Protection Act 1987 As responsible manufacturers, we take care to make sure that our products are designed and constructed to meet the required safety standards when properly installed and used. Firebricks, Fuel beds, Fuels - when handling use disposable gloves. Fire Cement - when handling use disposable gloves. In case of skin contact wash immediately with plenty of water.
General Gross Weight: 400kg Flue Outlet Diameter: 150mm Max Water Pressure: 1.79 Bar Minimum Flue Draught: 15 pa Boiler Water Capacity: 20 Litres SPECIFICATION Fig.1 *(Int.) *(Int.) WARNING:- THIS APPLIANCE MUST NOT BE USED WITHOUT WATER CONNECTED, OTHERWISE DAMAGE TO THE BOILER MAY BE CAUSED AND/OR HEAT DAMAGE TO SURROUNDING SURFACES. * (Int.
Advice on the test method can be obtained from HETAS. SITE PREPARATION The non-combustible hearth must be solid and level and together with the walls adjacent to the cooker and chimney, conform to current Building Regulations. When repairing or re-using chimneys its recommended that the building control office be consulted before the commencement of work with particular attention to the chimney height and its termination.
COOKER FLUE CONNECTION The position of available types of flue layouts are shown in Figs. 2, 3 and 4, the cooker flue chamber is adaptable to provide either top or back flue outlets, by means of the reversible loose socket. (a) Rear Flue Outlet This must only be used where there is a brick flue immediately behind the cooker. Provision must be made for a condensate collecting vessel and cleaning door. See Fig. 3. NOTE: MAXIMUM HORIZONTAL LENGTH 150mm. EXTENDED REAR FLUE PIPE AND BENDS ARE NOT RECOMMENDED.
There are two Isokern pumice liners which are also recommended. One is the standard 175mm diameter and the other is a 170mm thin wall. The thin wall has a smaller outer diameter and is designed to fit an existing chimney system. Both have a lifetime guarantee. An air vent outside the building should not be located less than the dimensions specified within the Building Regulations and B.S. 8303: Part 1 from any part of any flue terminal.
Fig.6 FLUE BOX Apply fire cement to the socket in the hob. Attach a short length of 6” (150mm) I.D. pipe approx. 10” (250mm) long to the outlet of the flue box by means of fire cement. Place the flue box on the hob and the pipe into the wall and consolidate the fluebox and pipe into the fire cement. Apply 3 or 4 coils of 10mm (1/2’) insulating rope to the pipe and fill the wall cavity with fire cement. (See fig. 5).
HIGH UPDRAUGHTS TESTING & COMMISSIONING Tall chimneys may develop excessively high updraughts which prevent the appliance operating correctly. After completing the installation, the heating contractor should demonstrate to the user the operation of the appliance and the routine cleaning method. It is recommended that a proprietary brand adjustable flue draught stabiliser having an openable cross sectional area of 182.
EXPLODED VIEW 10
PARTS LIST No. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. 46. 47. 48. 49. 50. 51. 52. 53. 54. 55. Description Code No.
With AGA Rangemster’s policy of continuous product improvement, the Company reserves the right to change specifications and make modifications to the appliance described at any time. Manufactured by AGA Rangemaster Station Road Ketley Telford Shropshire TF1 5AQ England www.rayburn-web.co.uk www.agacookshop.co.