User`s manual

5-5
5
Functions
5. Functions
FOT/ROT terminals
These terminals connect to operating range
limit switches in order to prevent overtravel.
FC-01 : Input terminal polarity setting
Related parameters
• When this signal is turned on, drive is allowed.
• To prevent overtravel, the internal speed command limit value in that direction is
set to 0.
• By changing the "Input terminal polarity" (FC-01) setting, drive is also allowed
when this input terminal is opened.
• An overtravel error (E25) occurs if the servo is ON for more than 1 second after the
FOT and ROT were both set to OFF.
• The FOT and ROT terminal function does not change even if the FA-14 (Motor
revolution direction) setting is changed. The FOT always prohibits drive in the CCW
direction and the ROT prohibits drive in the CW direction.
• When operating the robot with the RDP, the magnetic pole position estimation
should be performed with the FOT and ROT set to ON.
• A magnetic pole position estimation error (E95) occurs if either of the FOT or ROT
is set to OFF while the magnetic pole position is being estimated.
PEN terminal
The position command pulse input is valid
(enabled) only when this signal is ON.
FC-01 : Input terminal polarity setting
Related parameters
• The position command value can be refreshed by pulse train input while this signal
is ON.
• The "Input terminal polarity" (FC-01) setting allows position pulse train input to be
enabled when this input terminal is opened.
CER terminal
This signal clears the deviation (position error)
counter to "0" by setting the position command
value as the current position during position
control.
FC-01 : Input terminal polarity setting
Related parameters
• This signal is only valid during position control. The position command value is set
to the current position value at the instant this signal is switched from OFF to ON.
Since this signal turns on at the pulse edge, the counter clearing does not continue
even if this signal is kept ON. To clear the counter again, set this signal to OFF and
then back ON again.
• By changing the "Input terminal polarity" (FC-01) setting, the deviation counter can
also be cleared when this input terminal is opened.