User`s manual

Installation and wiring
3
3-24
3. Installation and wiring
4) Position command signal
Connect the pulse train signal for position command. As shown in the figure
below, the line receiver receives a pulse train signal output from the line driver
(AM26LS31 or equivalent) of the master controller.
Each position command signal cable should be a shielded, twisted pair cable.
Connect the cable shield to ground (
) on the robot driver side. (The I/O
connector case of the robot driver is internally connected to the ground.)
1507
PLSP,
SIGP
PLSN,
SIGN
Line driver
(AM26LS31)
Shielded cable
Connector
case
Robot driver
Electrical specifications and timing chart for position pulse signals are shown in
the following table.
Electrical specifications for position command pulses
Item Unit Specifications Condition
Input current of logic 1 mA 8 to 15
Maximum input
pulse rate
(Frequency)
• FWD/REV pulse
input
• Command pulse
+ sign input
pulses/s 2M
Line driver
signal
• Phase difference
90° pulse input
pulses/s 500k
Line driver
signal