User`s manual
Installation and wiring
3
3-18
3. Installation and wiring
Type
Terminal
symbol
Terminal name Description
Electrical
specifications
Output
signal
SRD
SRDE
Servo ready
This signal is output when the servo
is ready to turn on (with main power
supply turned on and no alarms
tripped.)
Open collector
and emitter
signal output
+30V DC or
less, 50mA
max. per
output
ALM
ALME
Alarm
An alarm signal is output when an
alarm has tripped. (This signal is ON in
normal state and OFF when an alarm
has tripped.)
INP
INPE
Positioning complete
This signal is output when the deviation
between the command position and
current position is within the preset
positioning range.
Relay
output
BK
(B24)
(Note 1)
Brake release relay
output
When the servo is ON, this terminal
outputs a signal to allow releasing the
brake. (FLIP-X series only)
24V DC
375mA max.
Monitor
output
AO1 Monitor output 1
Outputs speed detection values, torque
commands, etc. as analog signal
voltages for monitoring.
Signals to output are selected by
setting parameters.
These signals are only for monitoring.
Do not use for control.
0 to ±3.0V
Load
impedance:
3k
Ω
or more
AO2 Monitor output 2
L
Monitor output
common
This is the ground for the monitor
signal.
Position
command
PLSP
Position command
pulse
(pulse signal)
Select one of the following signal forms
as the pulse-train position command
input.
(1) Command pulse + direction signal
(2) Forward direction pulse train +
reverse direction pulse train
(3) Phase difference 2-phase pulse
Line driver
input
PLSN
SIGP
Position command
pulse
(sign signal)
SIGN
Position
sensor
monitor
OAP
Position sensor
Phase A signal
Outputs monitor signal obtained by
dividing "phase A" signal of position
sensor.
Line driver
signal output
OAN
OBP
Position sensor
Phase B signal
Outputs monitor signal obtained by
dividing "phase B" signal of position
sensor.
OBN
OZP
Position sensor
Phase Z signal
Outputs monitor signal for position
sensor "phase Z" signal.
OZN
OZ Phase Z detection
Outputs monitor signal for position
sensor "phase Z" signal.
Open collector
output +30V
DC or less,
50mA max.
L
Phase Z detection
common
Brake
power
input
B24
(Note 1)
Brake power input
Input 24V DC brake power to this
terminal
24V DC input
B0
(Note 1)
Brake power common
Common terminal input for brake
power
Note 1:B24, BO and BK are available only with RDX, and not with RDP.