User`s manual

Maintenance and Inspection
7
7-4
7. Maintenance and Inspection
7.3 Megger test and breakdown voltage test
Do not perform a megger test or voltage breakdown test. Semiconductor devices used in
the inverter main circuit may deteriorate if subjected to such a test.
7.4 Checking the inverter and converter
Use a tester or multimeter to check whether the module will operate correctly.
[Preparation]
1. Disconnect the externally connected power cables (L1, L2, L3, L1C, L2C), motor
connection cables (U, V, W), regenerative braking resistor (+) and RB, and external
DC power supply cables (+) and (–).
2. Prepare an analog tester or multimeter. (Use the 1-ohm resistance measurement
range.)
[Check method]
Measure the continuity at L1, L2, L3, U, V, W, RB, (+), and (–) on the robot driver
terminal block by alternately changing the polarity on the tester to determine if module
operation is satisfactory.
Note 1: First, measure the voltage across the (+) and (–) terminals on the terminal
block of the robot driver by using the DC voltage range on the multimeter to
make sure the smoothing capacitor is fully discharged. Then switch the
multimeter to measure resistance and start making the checks.
Note 2: In the non-conducting state, the reading should be nearly infinite. However,
the reading might not be infinite due to momentary conduction caused by
effects of the smoothing capacitor. In a conducting state, the reading is
usually several to several dozen ohms.
The reading might not always be the same depending on the device type and
tester. However, the reading is satisfactory if equal to other values.
Note 3: Remove the cables from (+) and () on the main circuit terminal block (all
models) and also remove the shorting bar or wire connected across terminals
B1 and B2.
Note 4: The robot driver has an internal DB circuit between the main circuit
terminals U and W, so the reading measured across the main circuit terminals
is different from those shown in the table.