CHAPTER 3 Operating Procedures
3 - 41
7- The mechanical system diagnostics window opens.
8- Turn off the servo ON signal, turn the RS terminal on and then back off, and exit
the mechanical system diagnostics mode.
9- Observe the waveform to determine whether or not to make measurements again.
When the resonance point is properly measured:
Proceed as directed below.
The waveform shown in Step 7- indicates that a relatively clear resonance
point is measured. Therefore, you may proceed to next notch filter setup.
However, if you make measurements again as indicated below, you might be
able to measure a quite clear waveform as shown below.
When the resonance point is not properly measured:
Edit the measurement frequency setting (a) so that the measurement
frequency is five times of a currently measured peak (similar to the pointed
summit of a mountain) that looks like a resonance point, repeat Steps 4- and
beyond until you obtain a clean measurement result. You should also edit
settings (b) through (g).
The measurement result you will obtain after changing the setting might look
like the figure below: