Installation Guide
©2019 RI   
REV 11.14.2019 
4 
JOBSITE TESTING 
1.  Before jobsite testing, the building envelope must be sealed (walls, 
roofing, windows, doorways etc., installed).  
2.  The installation area and materials to be installed shall be maintained 
at a minimum of 65°F (18.3°C) and a 85°F (29.4°C) for 48 hours 
before, during and for 48 hours after completion of the installation. 
Relative humidity level extremes should also be avoided. General 
recommended humidity control level is between 35–55%. If a system 
other than the permanent HVAC source is utilized, it must provide 
proper control of both temperature and humidity to recommended or 
specific levels for the appropriate time duration.  
3.  Test sites must be properly prepared and protected for the duration of 
testing to achieve valid results. 
4.  Surface Flatness for all Subfloors:  
1.  The surface shall be flat to 3/16” (3.9 mm) in 10 ft. (3050 mm) 
and 1/32” (0.8 mm) in 1 ft (305 mm). 
2.  To check flatness, place a 10 ft straight edge, string, laser level 
or use another suitable method on the surface and measure the 
gap.  
5.  Concrete Subfloors:  
1.  Concrete subfloors must be finished and cured, free of all 
sealers, coatings, finishes, dirt, film forming curing compounds, 
or other substances that may prevent proper bonding of the 
flooring materials (ACI 302.1 and ASTM F710).  
2.  Randomly check concrete subfloor for porosity using the drop 
water test. Place a 1-inch diameter drop of water directly onto 
the concrete subfloor. If the water droplet does not dissipate 
within 60 to 90 seconds, the subfloor is considered non-porous.  
3.  Concrete subfloors must have a minimum compressive strength 
of 3,000 psi. Concrete subfloors shall not consist of lightweight 
concrete or gypsum.  
4.  Moisture Testing: Perform either the preferred In-situ Relative 
Humidity (RH) Test (ASTM F2170) or the acceptable Moisture 
Vapor Emission Rate (MVER) Test (ASTM F1869). For acceptable 
moisture limits please refer to the specifications of the adhesive 
being used.  
5.  Alkalinity: Must test surface alkalinity (ASTM F710). A 7.0 to 9.0 
pH is acceptable.  
6.  Wood Subfloors and underlayment panels shall have the 
moisture content tested using a suitable wood pin meter. 