CHAPTER 4: ADMINISTRATIVE FUNCTIONS 67
Configuring the Power Strip
1. Once the power strip has been added, KX Manager will automatically recognize that a power device is
connected. The Device Tree in the left panel of the window will change the appropriate target icon to
indicate that a power strip is connected to that port.
2. Select the power strip icon, right-click on it, and click Properties. When the Power Strip Properties
screen appears, type a name for the new power strip and click [OK].
3. In the Devices Tree, select the target server(s) powered through the power strip. Right-click on the
server icon and click Properties. The PC Properties window appears.
Figure 66 Associating a Target with a Power Outlet
4. Click on one of the Power Strip cells in the table and a list of available power strips connected to the
Dominion KX appears. Click on the appropriate power strip.
5. Click on the Outlet cell in the same row as the power strip selected. A list of available outlets appears;
select the outlet to which the device is connected.
6. Repeat these steps for all devices plugged into multiple outlets.
Once outlets have been assigned, Remote Power Management to the associated server will be available
through RRC.
Note: Be sure to assign the correct outlets to each channel. If more than one outlet is physically associated
with a different server, you could accidentally switch OFF the wrong server.