Brochure
FASTPIPE INSTALLATION STEPS
1) CUT PIPE TO LENGTH with tubing cutter (cut must be square)
(DO NOT USE HACK SAW )
2) DEBURR the end of the pipe outside and inside
3) MARK END OF PIPE for the proper insertion depth
1” Fittings: 2-3/4 inches
3/4” Fittings: 2 inches
2” Fittings: 4-3/4 inches
3” Fittings: 4-1/2 inches
1-1/2” Fittings: 4 inches
4) WET END OF PIPE, with very diluted soapy water
DO NOT USE ANY OIL OR GREASE LUBRICANT
5) LOOSEN FITTING CONE NUT PARTIALLY
LOOK INSIDE EACH FITTING FOR INNER PARTS
(inner parts, o-ring, stainless steel bite ring)
6) INSERT PIPE
HAND TIGHTEN
FULLY TIGHTEN
FASTPIPE INSTALLATION GUIDELINES
-CHECK that all fittings are fully tightened before pressurizing the system for the first time.
-for initial installation, pressurize system slowly to 50 psi and check for leaks, then pressurize slowly to MAX 190 psi
-Always use a filter unit to keep contaminants out of the FastPipe system.
-take extra precaution with END CAP INSTALLATION, double check these fittings are tightened fully.
-Assemble all NPT threads with two wraps of teflon tape and then PIPE SEALANT which prevents thread galling.
-FASTPIPE can be bent to conform around minor obstacles to a maximum of 15 degrees. DO NOT OVERBEND
-USE JUMPER HOSE at the air compressor to absorb vibration
-ONLY FastPipe outlets are designed for the direct pulling force of air hoses, for other FastPipe fittings attached to
hoses, always secure hose with a STRAIN RELIEF, attached to the building structure
may have loosened due to settling of the component.
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
TAB MUST ALIGN TO NOTCH
-After the first 48-96 hours of operation, check all the joints. Then make sure all the cone nuts are tight as these
FLAT SURFACE INSTALLATION
Ceiling or wall mount
Clip has 5/16” thru hole and hex bore for a 5/16” hex nut
Hex nut serves as a backer for screws
In horizontal installations, mount clip pivot tab up
-Beam clamp-Pipe Clip
-5/16” theaded rod
-Pipe Clip
-Thru hole design
-works for both 5/16”
and 3/8” threaded rod
-3/4” width opening
-for 3/8”-16 threaded rod
-12” overall length
-silver zinc plated
(green for picture
purpose only)
-for 1-5/8” standard strut
-Beam Clamp
-3/8” threaded rod
-Loop hanger
-Cantilever arm
-Cantilever tube supports
HANGING INSTALLATION
X
6” D max = 10 FT
MAIN
SIZE
PART
NUMBER
X
DIMENSION
3/4”
F1022-10
15
/16 ”
1”
F2022-10
7
/8”
2”
F5022-10
3
/4”
1
1
/2”
F4022-10
(Pack of 10)
1
1
15
/16 ”
PART NUMBER
F0018
PART NUMBER
F0021
MAIN
SIZE
PART
NUMBER
3/4” & 1”
F0019
2”
F0024
3”
FI0030
1
1
/2”
F0020
MAIN
SIZE
PART
NUMBER
1”
F0022
3/4”
F0017
2”
F0025
3”
FI0028
1
1
/2”
F0023
BEAM CLAMP
PIPE CLIP
LOOP HANGER
CANTILEVER ARM
CANTILEVER TUBE SUPPORT
- hangers or mounting clips should be no more than 10 ft apart and one must be at least 6” from a fitting
- do not over tighten cantilever type tube supports, pipe must be allowed to expand and contract slightly in length
- for continuous lengths over 200 ft and variations in temperatures of 80 deg F consult the factory for
expansion joint guidelines