Owner's manual
9060 High Voltage Controller - Wiring Configurations
CP-13-05.3 52
Remote Analog Current Control (Sourcing Configuration)
The following example configuration uses the following:
•
Sourcing Configured Digital Inputs (Apply 24VDC to activate the input)
•
Permanently Wired into Remote Mode (Jumper Wire from TB3-10 to TB3-2)
•
Normally Open (NO) Contact to Activate Reset when unit is Faulted
•
Normally Open (NO) Contact to Activate HV Trigger to turn on HV Cascade
•
0-20mA Analog Current Control Signal
Figure 45: Remote Analog Current Control (Sourcing Configuration)