9060 High Voltage Controller - Wiring Configurations
51 CP-13-05.3
WIRING CONFIGURATIONS
COMMON REMOTE CONFIGURATIONS
Remote Analog Voltage Control (Sourcing Configuration)
The following example configuration uses the following:
Sourcing Configured Digital Inputs (Apply 24VDC to activate the input)
Permanently Wired into Remote Mode (Jumper Wire from TB3-10 to TB3-2)
Normally Open (NO) Contact to Activate Reset when unit is Faulted
Normally Open (NO) Contact to Activate HV Trigger to turn on HV Cascade
0-10V Analog Voltage Control Signal
Figure 44: Remote Analog Voltage Control (Sourcing Configuration)