Use and Care Manual

44
X. BURNER SPECIFICATIONS
TABLE 13: BECKETT AFG BURNER SPECIFICATIONS
Beckett AFG
Boiler Model
Firing Rate
GPH
Settings Nozzle
3
Pump
Pressure
Head
(Setting)
Air
Shutter
Air
Band
GPH x Angle Type
2
Shipped
1
RRO080
0.65 L1 8 0 0.55 x 70B (Delavan) Loose 140
RRO092 0.75 L1 6 0 0.65 x 45B (Hago) Loose 140
RRO120 1.00 L1 10 1 0.85 x 45B (Hago) Installed 140
RRO111 0.90 L1 7 0 0.75 x 45B (Delavan) Installed 140
RRO151 1.25 V1(0) 10 1 1.00 x 45B (Hago) Loose 175
RRO179 1.50 V1(3) 10 2 1.10 x 45B (Hago) Installed 175
1
Beckett low ring rate bafe required on RRO080 (0.65 GPH) application only; shipped loose with nozzle.
2
Nozzle(s) for alternate boiler model ring rate(s) are shipped loose in bag attached to the
burner.
3
Single stage fuel pump is standard. Burner manufacturer has preset single stage fuel pump to settings shown in
table above.