Use and Care Manual
36
B.  OIL PRIMARY CONTROL (Oil Primary)
1.  Burner (Oil Primary) will not come on.
a.  No power to Oil Primary.
b.  Oil Primary is in lockout or restricted mode. 
Press reset button for one (1) second to exit 
lockout. If control has recycled three times 
within the same call for heat, it will enter into 
restricted mode. To reset from restricted mode, 
refer to Section V, Paragraph I, Step 2 for details.
c.  CAD cell seeing light.
d.  CAD assembly defective.
e.  Control motor relay is stuck closed (see note 
below).
2.  Burner (control) will light, then shut down after a 
short time, then restart after one (1) minute.
a.  CAD cell is defective.
b.  Air leaking into oil line causing ame out.
c.  Defective nozzle causing ame to be erratic.
d.  Excessive airow or draft causing ame to leave 
burner head.
e.  Excessive back pressure causing ame to be 
erratic.
3.  Control locks out after Trial For Ignition (TFI).
a.  No oil to burner.
b.  Shorted electrodes.
c.  Nozzle clogged.
d.  Airow too high.
e.  Ignitor module defective.
f.  CAD cell defective.
g.  Oil valve stuck open or closed.
Note: The Safety Monitoring Circuit (SMC) is 
 designed to provide lockout in the event of a 
 stuck or welded motor relay.
  Also refer to Model EZ-1/2/3 Oil Burner - Instruction 
Manual (Form #MNEZ123) for additional information.
NOTICE
If ame is not established within 15 seconds of 
oil valve actuation (known as Trial For Ignition 
[TFI]) lockout will occur. Lockout is indicated 
by a red LED solid-on located on the oil primary 
control.
Hard Lockout will occur if the Oil Primary 
Control locks-out three (3) times during a call 
for heat. This is indicated by red light reset 
button solid-on.
C.  INTELLIGENT OIL BOILER CONTROL
 •ColdStartBoilerControlis used on Boilers without 
 Tankless Heaters.
  • Warm Start Boiler Control is used on Boilers with 
 Tankless Heaters
1.  When a problem occurs with the boiler operation, 
the Boiler Control easily provides specic, valuable 
information to help resolve the issue quickly. The 
display on the Boiler Control should be the rst 
place to check.
a.  If an Error Code "Err" IS NOT displayed on 
the Boiler Control: In this circumstance, Table 
11 can be used to determine the problem and 
possible causes.
System Condition Diagnostic Condition Check Action
Boiler is cold, house is 
cold.
Display is OFF. 120 Vac System power. Turn system power on.
Display is ON. 24 Vac T-T No 24 V; replace control.
24 V present; disconnect 
thermostat, short T-T.
Boiler starts, check wiring and thermostat.
120 Vac at B1-B2
• If no, replace control.
• If yes, check burner and wiring.
Refer to Err on display. -----
Boiler is hot, house is 
cold.
Display is ON.
120 Vac at C1-C2
• 120 Vac at C1-C2, check wiring to 
pump.
• Wiring OK, is pump running?
• If not, replace the pump.
• If pump is running, check for trapped air   
 or closed zone valves
Boiler below the Low Limit 
temperature, wait for boiler to go 
above Low Limit temperature.
-----
Boiler above LL? If yes, check 
for 120 Vac between ZC and L2.
• If no 120 Vac , replace control. 
• If yes, check zone relays, circulators 
 and wiring.
TABLE 11: TROUBLESHOOTING GUIDE