Use and Care Manual
11
110637-01 - 5/20
RRO Installation & Service Manual
 A.  EVALUATE THE EXISTING WATER SYSTEM.
  Design a piping system and install boiler which 
will prevent oxygen contamination of boiler water 
and frequent water additions.
1.  There are many possible causes of oxygen 
contamination such as:
a. Addition of excessive make-up water as a 
result of system leaks.
b. Absorption through open tanks and fittings.
c. Oxygen permeable materials in the 
distribution system.
 2. In order to insure long product life, oxygen 
sources must be eliminated. This can 
be accomplished by taking the following 
measures:
a. Repairing system leaks to eliminate the 
need for addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing fittings which 
allow oxygen absorption.
d. Use of non-permeable materials in the 
distribution system.
e. Isolating the boiler from the system water by 
installing a heat exchanger.
  WARNING
 System supply and return piping must be 
connected to correct boiler pipe.
  U.S. Boiler Company recommends sizing 
the system circulator to supply sufficient 
flow (GPM) to allow a 20°F temperature 
differential in the system. When sizing the 
system circulator, the pressure drop of all 
radiators, baseboard and radiant tubing and all 
connecting piping must be considered.
CAUTION
 Maintain minimum ½ inch clearance from hot 
water piping to combustible materials.
B.  CONNECT SYSTEM SUPPLY AND RETURN 
PIPING TO BOILER. See Figures 4-2 and 
4-3. Also, consult Residential Hydronic Heating 
Installation and Design I=B=R Guide. 
1. If this boiler is used in connection with 
refrigeration systems, the boiler must be 
installed so that the chilled medium is piped 
in parallel with the heating boiler using 
appropriate valves to prevent the chilled 
medium from entering the boiler. See Figure 
4-1. Also, consult Residential Hydronic 
Heating Installation and Design I=B=R Guide.
2. If this boiler is connected to heating coils 
located in air handling units where they may 
be exposed to refrigerated air, the boiler piping 
must be equipped with flow control valves 
to prevent gravity circulation of boiler water 
during the operation of the cooling system.
3.  If boiler is used with an Indirect Domestic 
Water Heater, install the Indirect Water Heater 
as a separate heating zone. Refer to the 
Indirect Water Heater Installation, Operating, 
and Service Instructions for additional 
information.
4. Use a boiler bypass if the boiler is to be 
operated in a system which has a large 
volume or excessive radiation where low boiler 
water temperatures may be encountered (i.e. 
converted gravity circulation system, etc.) 
The bypass should be the same size as the 
supply and return lines with valves located 
in the bypass and return line as illustrated in 
Figures 4-2 and 4-3 in order to regulate water 
flow for maintenance of higher boiler water 
temperature. 
  WARNING
 The use of a low water cut-off device, while 
not required unless radiation level is below the 
boiler, is highly recommended.
5.  If a Low Water Cut-Off (LWCO) is required, it 
must be mounted in the system piping above 
the boiler. The minimum safe water level of a 
hot water boiler is just above the highest water 
containing cavity of the boiler; that is, a hot 
water boiler must be full of water to operate 
safely. Refer to Appendix A at the rear of this 
manual.
6.  If it is required to perform a long term 
pressure test of the hydronic system, 
the boiler should first be isolated to avoid a 
pressure loss due to the escape of air trapped 
must first be removed from the boiler.
4 Water Boiler Piping and Trim
!
!
!










