Installation Guide

9
6.  Installation of manual shutoff valve located above 
the LWCO and the boiler is recommended to allow 
servicing. Thus LWCO probe can be removed for 
inspection without draining the heating system. An 
annual inspection of the probe is recommended.
7.  The presence of water covering properly installed 
LWCO probe will cause the normally open contact 
of the LWCO to close, thus providing continuity of 
the 24 VAC service to the boiler gas valve. When 
water level drops below probe, LWCO contact 
opens up breaking 24V supply to gas valve and 
preventing the boiler to re.
8.  RRG Series gas hot water boilers have a “plug-in” 
provision in the factory wiring that will accept an 
optional 24VAC probe LWCO harness connector. 
The optional LWCO kit includes a 24VAC probe 
LWCO, Harness and Instructions addressing piping, 
wiring and testing after installation. See Figure 9 for 
wiring of the LWCO. Contact your local Rand & 
Reardon Distributor for LWCO Kits.
9.  RRG Series gas hot water boilers have a "plug-
in" provision in the factory wiring that will accept 
an optional Auxiliary High Limit harness. The 
optional Auxiliary High Limit, Well, Harness and 
Instructions addressing piping, wiring and testing 
after installation. Contact your local Rand & 
Reardon Distributor for Auxiliary High Limit Kits.
 10. Provisions are provided so that both the Optional 
LWCO Kit and the Auxiliary Kit can be installed on 
the same boiler.
Figure 6: Recommended Probe LWCO Location
I.  Optional LWCO and Auxiliary High Limit 
Installation
WARNING
DO NOT ATTEMPT to cut factory wires to 
install an aftermarket Low Water Cut Off 
(LWCO). Only use connections specically 
identied for Low Water Cut Off.
In all cases, follow the Low Water Cut Off 
(LWCO) manufacturer’s instructions.
1.  A low water cutoff is required to protect a gas-red 
hot water boiler when any connected heat distributor 
(radiation) is installed below the top of the hot water 
boiler (i.e. baseboard on the same oor level as 
the boiler). In addition, some jurisdictions require 
the use of a LWCO with a hot water boiler as a 
redundant safety control.
  It is recommended that the LWCO control is 
installed above the boiler to provide the highest 
level of protection. However, where the LWCO 
control is approved by the LWCO control 
manufacturer for installation in a high boiler tapping 
of a water boiler, the use of the listed LWCO control 
is permitted when it is installed according to the 
LWCO manufacturer's instructions. 
2.  The recommended location for a LWCO on gas 
hot water boilers is above the boiler, in the supply 
piping. The minimum safe water level of a water 
boiler is at the uppermost top of the boiler; that is, it 
must be full of water to operate safely.
3.  Typically, in residential applications, a probe type 
LWCO is used instead of a oat type, due to their 
relative costs and the simplicity of piping for a 
probe LWCO.
4.  Piping and ttings required to install LWCO are 
eld supplied.
5.  When constructing a piping tree to install LWCO 
select ttings (tees, elbows etc) and nipples to have 
the same size (NPT) as boiler supply connection. 
At minimum, 1-1/4” tee with ¾” branch outlet is 
required to connect the probe LWCO to the supply 
piping. See Figure 6 for location and piping of 
the LWCO. DO NOT REDUCE THE SIZE OF 
NEAR BOILER SUPPLY FITTINGS AND 
NIPPLES.










