Product Overview

Temperature [°C]
F59
Setpoint 1
Time [s]
[Allo]
Minimum
Temperature
Alarm duration
Inhibition
time (F61)
Digital input alarm [AlIn]
When the door open alarm is enabled (F52) and is activated, a [AlIn] type record will be carried out.
In this case, the information stored is: alarm start date and time, alarm duration, and maximum
temperature measured during the alarm condition.
Door
Time [s]
Open
Closed
Alarm duration
F51
[AlIn]
Power failure alarm [AlNo]
If there is a power failure and the controller stays off for more than 1 minute, when the power is restored
and the controller presents a temperature exceeding the value configured in F60 (HACCP - High
temperature alarm), a [Alno] type record will be immediately created. In this case, the information
stored is: power restoration date and time, and temperature measured at the moment the controller is
switched on again.
Temperature [°C]
F60
Setpoint 1
Time [s]
[Alno]
Controller off
Up to six records for each type of alarm are stored. If the number of records stored exceeds this number,
the least recent record is replaced for each new alarm.
The HACCP alarms display must be made in [HACC] in the main menu or in the quick access menu
(;). The [HACC] menu is divided in accordance with the type of alarm:
[ALHi]: where the high temperature records are;
[ALLo]: low temperature records;
[AlIn]: digital input records;
[Alno]: power failure records.
Follow the steps below to view the records:
a) Select option [HACC] in the main menu and press /.
b) Choose the type of alarm to be viewed [ALHi], [ALLo], [AlIn] or [Alno] using the buttons
< or > and press/.
c) The controller stores up to six records for each type of alarm, use the buttons < or > the number of
the record to be viewed and press /.
[HACC]
/
[ALHi]
/
[,Hi1]
[,Hi6]
[ALLo]
>
[AlIn]
[Alno]
.
.
.
/
[,lo1]
[,lo6]
.
.
.
>
/
[,no1]
[,no6]
.
.
.
>
/
[,In1]
[,In6]
.
.
.
[,--d][,--m][,--y][00:00][stay]
[00:00][temp][,00.0]
/
[,--d][,--m][,--y][00:00][temp]
[,00.0]
/
[,--d][,--m][,--y][00:00][stay]
[00:00][temp][,00.0]
/
[,--d][,--m][,--y][00:00][stay]
[00:00][temp][,00.0]
/
NOTE: Keep the button / held down to return to the previous menu page.
NOTE 2: The alarm duration time and maximum temperature measured can be updated while the alarm
is occurring.
Follow the steps below to erase all HACCP alarm records:
a) Go to the main function menu pressing < and> (quick touch) simultaneously while the
temperature is displayed.
b) Select the menu option[Code] and press/.
c) Using the< or> keys enter the access code 123 (one hundred and twenty-three) and confirm
with/.
d) Using the<or>, keys again, enter the [HACC] menu, select option [Hrst] and press /.
e) If you are sure you want to erase the HACCP records permanently and the code was entered
correctly, use the<or> keys, select option [,yes]and press/.
f) The message [rset] will be displayed and all HACCP records will be erased. From this moment on,
any newly generated HACCP alarm will be stored in position 1 of the alarm category to which it belongs.
HACCP Signaling
When a new HACCP alarm occurs, the indication ( ) in the display will be lit. The indication will only go
dark after the alarm is viewed in the [HACC]menu.
For easy viewing of the new HACCP alarms, the dot in the lower right corner of the alarm type will be lit,
indicating which alarms have not yet been displayed, as shown in the figure below.
[HACC]
/
[ALHi.]
/
[,Hi1.]
[,Hi6]
.
.
.
High temperature alarm [AlHi]
During operation, when a temperature exceeding the value configured in F60 (HACCP - High
temperature alarm) is identified and stays above this value for a time exceeding the value configured in
F61 (Alarm validation time), an [AlHi] type record is created. In this case, the information stored is:
alarm start's date and time, alarm duration, and maximum temperature measured during the alarm
condition.
Temperature [°C]
F60
Setpoint 1
Time [s]
[AlHi]
Maximum
temperature
Alarm durationInhibition
time (F61)
Low temperature alarm [AlLo]
During operation, when a temperature below the value configured in F60 (HACCP - Low temperature
alarm) is identified and stays below this value for a time exceeding the value configured in F61 (Alarm
validation time), a [AlLo] type record is created. In this case, the information stored is: alarm start
date and time, alarm duration, and minimum temperature measured during the alarm condition.
d) In [AlHi], [ALLo] and [AlIn] type alarms, the following data will be displayed in sequence:
alarm start date and time ([,--d][,--m][,--y][00:00]), alarm duration ([stay][00:00])
maximum / minimum temperature measured during the alarm.
e) In[Alno]type alarms, the following data will be displayed in sequence: alarm start date and time
([,--d][,--m][,--y][00:00]) and temperature measured at the moment power is restored.
f) If there are no records stored in the chosen option, the message [,nop]will be displayed.
g) After displaying the alarm data, the controller returns to the HACCP alarm display menu.
6.4 Advanced Operations
6.4.1 Access to the main menu
The main menu can be accessed through the quick access menu, option [Func]or by pressing <
and> simultaneously (quick touch) while the temperature is being displayed.
The following options will be displayed:
[Code]- Entry to the access code
[Func]- Change the parameters
[Log,]- Datalogger functions
[ClO,]- Adjustment or visualization of the date and time
[HACC]- Display of the HACCP alarms
6.4.2 Access Code
To change the parameters or adjust the clock, select the[Code]option by pressing /(quick touch)
and entering the access code 123 (one hundred and twenty-three) using the<or>key, and confirm
with/.
6.4.3 Changing the controller parameters
In the main menu, enter the option [Func] and select the desired function using the <or>keys.
Press/(quick touch) after selecting the function to view its value. Use < or> to change the value
and press/when ready to save the configured value and return to the functions menu. To leave the
menu and return to the normal operating mode (temperature indication), hold down /(long touch) until
[----]appears.
NOTE: If the functions lock is active, the controller will show the message [LOC,]in the display upon
pressing<or>and will not allow adjusting the parameters.
6.4.4 Date and time adjustment
Select the option [ClO,]in the main menu. The controller will enter the date and time adjustment
mode if the access code [,123] was correctly entered. Use <or> to change the value and press
/ when ready to save the configured value. If the date entered is invalid, the message [ECLO] will be
shown on the display.
IMPORTANT: The controller has an auxiliary internal power supply to keep the clock running in
case of power failure. If the controller remains off for a long period of time, the message [ECLO] will be
displayed to indicate that the clock is not programmed. In this case, the date and time must be adjusted
and the controller must be kept on for 24 hours to fully recharge the auxiliary power supply.