Product Overview

FOUR-STAGE DIGITAL CONTROLLER WITH
ALARM, CYCLICAL TIMER, SERIAL
COMMUNICATION, AND HACCP FUNCTIONS
MT543ELOGV03-01T-15724
evolution
MT-543e Log
V
er.03
Functions
lock
Serial
programming
Degree of
protection
IP 65
FRONT
Audible
alarm
Cyclical
timer
Supervisory
system
WARNING
ACCESSORIES:
Only use original accessories of Full Gauge Controls.
If you have any questions, please contact our technical support.
AUTHORIZED SERVICES:
The installation and maintenance of the product must only be performed by qualified personnel.
DUE TO CONSTANT EVOLUTION, FULL GAUGE CONTROLS RESERVES THE RIGHT TO CHANGE THE
INFORMATION CONTAINED IN THIS MANUAL.
BEFORE INSTALLING THE CONTROLLER WE RECOMMEND READING THE INSTRUCTION
MANUAL THOROUGHLY IN ORDER TO AVOID POSSIBLE DAMAGES TO THE PRODUCT.
PRECAUTIONS WHEN INSTALLING THE PRODUCT:
Before performing any procedure in this instrument, disconnect it from the mains; make sure the
instrument has proper ventilation, avoiding installation in panels containing devices that may force
it to work outside the specified temperature limits;
Install the product away from sources that can generate electromagnetic disturbances, such as:
motors, contactors, relays, solenoid valves, etc.
1. DESCRIPTION
2. APLICATIONS
The MT-543e Log controller has four stages that can be applied to refrigeration or heating: the first
stage, together with the third stage, works in systems that require minimum ventilation; the third one
works as a cyclical timer; the fourth one works as an alarm. The second, third and fourth stages work
also in the following modes: refrigeration, heating, refrigeration (Sp1), heating (SP1) and refrigeration in
rotation. It also has a fifth relay that can be used as power failure alert and / or alarm.
The MT-543e Log accepts three types of sensors: NTC thermistor (-50 to 105 °C*), PT100** and
PT1000** (-99 to 300 °C). It has an intelligent functions lock system, a mode to switch off the control
functions, an internal audible alarm (buzzer), and a configurable digital filter.
It allows the stages to be used in an independent way or in rotation mode (alternating the outputs). It
features an internal memory (datalogger), where the temperature value is stored in user-defined time
periods, the temperature variation and the state of the outputs. In addition, it has built-in rechargeable
battery and clock to keep track of data even in case of power failure and serial port for communications
with Sitrad.
It also allows monitoring of HACCP critical points (Hazard Analysis and Critical Control Point) by means
of records in the controller's memory of high temperature alarm, power failure, and digital input.
Blood banks Vaccines
Multistage temperature systems
Air conditioners
Datacenters
Note: Sensor cable length can be increased to up to 200 meters by the user by using a PP 2 x 24 AWG
cable.
*It measures temperatures up to 200 °C using the SB59 (sold separately).
**This sensor is sold separately.
3. TECHNICAL SPECIFICATIONS
Control temperature
*NTC: -50 to 200ºC / -58 to 392ºF
**PT100: -99 to 300ºC / -146 to 572ºF
**PT1000: -99 to 300ºC / -146 to 572ºF
Power supply
MT-543E Log: 100~240 Vac (50/60 Hz)
MT-543EL Log: 12 or 24 Vac/dc +10%
Operating temperature
0 to 40ºC / 32 to 104ºF
Operating humidity
10 to 90% UR (no condensation)
Dimensions (mm)
76 x 34 x 77 mm (WxHxP)
Maximum output current
OUT1, OUT2, OUT3, OUT4: 5(3)A / 250 Vac / 1/8HP
OUT5 (NF): 1A / 250Vac
Dimensions of the clip for fixing the
instrument
71 ± 0,5 x 29 ± 0,5 mm (see item 5)
4. 4. INDICATIONS AND KEYS
MT-543e Log
Set key
Quick access
menu key (Flatec)
Temperature unit indication
LED
Increase key
Decrease key
Led indicator
(digital output 1 on / off)
Led indicator
(digital output 2 on / off)
Led indicator
(digital output 3 on / off)
Led indicator
(digital output 4 on / off)
HACCP led indicator
5. INSTALLATION - PANEL AND ELECTRIC CONNECTIONS
Panel (front view)
Panel
(side view)
Dimensions of the opening
to fasten the instrument
71 mm± 0,5
29 mm± 0,5
FOR INSTALLATIONS THAT REQ UIRE WAT ER
TIGHTNESS, TO INSTALL THE CONTROLLER THE
OPENING MUST BE 70.5 x 29 mm MAXIMUM.
THE SIDE LATCHES MUST BE FIXED SO THAT
PRESSURE IS APPLIED TO THE SEALING GASKET TO
PREVENT INFILTRATION BETWEEN THE OPENING AND
THE CONTROLLER.
WARNING
1
5
6
7
8
2
3
4
9
POWER
SUPPLY
10
11 12
13
14
15 16
17
90~264Vac
100~240Vac
connection
COMMON 1
1
5
6
7
8
2
3
4
9
POWER
SUPPLY
10
11 12
13
14
15 16
17
1
5
6
7
8
2
3
4
9
POWER
SUPPLY
10
11 12
13
14
15 16
17
12 Vac/dc
connection
12 Vac/dc
24 Vac/dc
24 Vac/dc
connection
A
B
SITRAD
NTC*
PT100**/ PT1000**
COMMON 2
OUT 1
OUT 2
OUT 3
OUT 4
A
B
SITRAD
NTC*
PT100**/ PT1000**
NTC*
PT100**/ PT1000**
A
B
SITRAD
0
0
COMMON 1
COMMON 2
OUT 1
OUT 2
OUT 3
OUT 4
COMMON 1
COMMON 2
OUT 1
OUT 2
OUT 3
OUT 4
6. OPERATIONS
6.1. Quick Access Menu Map
To access or browse the quick access menu, use the ; key (quick touch) while the temperature is being
displayed by the controller. With each touch the next function in the list is displayed. To confirm use the
/ key (quick touch). See chapter 6.3 for more details. The map of functions is shown below:
MT-543
e
Log
MT-543
e
Log
HACCP
function
COMMON 3
OUT 5
COMMON 3
OUT 5
COMMON 3
OUT 5
;
ADJUSTING DESIRED
TEMPERATURE (SETPOINT)
;
FUNCTIONS LOCK
;
CONTROL FUNCTIONS
SHUTDOWN
MIN. AND MAX.
TEMPERATURE RECORD
;
;
ALARM INHIBITOR
FUNCTION SELECTION
;
MT-543e Log
MT-543e Log
MT-543e Log
MT-543e Log
MT-543e Log
MT-543e Log
;
;
MT-543e Log
EXIT FUNCTION
;
MT-543e Log
;
ERASE MAX. AND
MIN. VALUES
MT-543e Log
;
HOUR METER VIEW
MT-543e Log
;
DATE AND TIME VIEW
MT-543e Log
MT-543e Log
;
RESET OF THE
HOURMETERS
MT-543e Log
D1
D1
D1
6.2. Quick access keys map
When controller is on temperature display mode, the following keys can be used as shortcuts for the
following functions:
Hold down for 2 seconds: Setpoint adjustment.
/
Quick touch: day/month/year/hour/minute.
/
Approximate consumption
0,6 VA
Datalogger
LOG
Have this manual to hand when
using the FG Finder application.
IMPORTANT
3/32'' (2.4 mm) SLOTTED SCREW DRIVER FOR ADJUSTMENTS
IN THE SIGNAL TERMINALS;
#1 PHILLIPS SCREW DRIVER FOR ADJUSTMENTS IN THE
POWER TERMINALS.
IT IS ESSENTIAL TO USE PROPER TOOLS IN ORDER TO AVOID
DAMAGES TO THE INSTRUMENT'S CONNECTION TERMINALS:
** This sensor is sold separately.
DATALOGGER ON/OFF
(MANUAL MODE)
HACCP ALARMS DISPLAY

Summary of content (8 pages)