Installation and Operations Manual V1.4 Ramtech Electronics Limited 2018
Emergency Call Point Technical Data
Model Numbers: W3-ECP-CSS-N-9X
Device Parameters
Dimensions (mm) HxWxD: 235 x 161 x 128 (excl. antenna 81mm and USB 15mm)
Weight: 1.7kg
Operating temperature: -13°F to +158°F (-25°C to +70°C)
Humidity: Relative humidity >95% (77°F to 131°F)
IP Code: IP55C
Main sound frequencies & patterns: 800Hz to 970Hz swept at 1Hz
Minimum A-weighted sound at 1 metre
Position Horizontal Plane dB(A) Vertical Plane dB(A)
15 83.7 85.3
45 89.4 91.6
75 96.5 94.8
105 96.5 97.6
135 90.4 91.3
165 85.0 83.9
Supply Parameters
Operating voltage range: 4.4-6.4V from internal battery
Power: 620μW average
Current consumption: 120μA average
Battery type: Alkaline primary cells, 23Ah
RF Parameters
Operating frequency: 916.5MHz
Transmit power: 25mW max
Duty cycle: <1%
Encryption: None
Channel spacing: Single channel
Compatible with: Other WES
3
units
Protocol: Proprietary