Installation and Operation Manual

Page 15 WES
3
Installation and Operations Manual V1.4 Ramtech Electronics Limited 2018
At the end of the re-arming period the Emergency Control Unit will
return to the home screen unless any system warnings have been
received during the re alarm or re-arm period
System Warnings
The Emergency Control Unit will indicate warnings from itself or any
other system unit. When a warning is received the LCD will ash and
the unit will beep periodically.
Warnings are displayed in the format: date, time, unit number and type,
warning type. Some warnings, for example EXT, will self-clear if the
fault is resolved.
Alarm
When an alarm has been raised by a Emergency Call Point or Sensor,
the Emergency Control Unit will ash the LCD display, beep and
display ALARM ALARM ALARM together with which units raised the
alarm. The newest event will be at the top of the list.
Units are identied by unit number and unit type. F indicates a
Emergency Call Point, I an Interface and S a Sensor. For example, the
above shows that a Emergency call point with the number 001 was
activated at 08:53 on the 7th June.
An alarm can be silenced in three ways:
i) Resetting a call point
ii) Waiting 30 minutes after the last activation
iii) Using your access code to silence the alarm from the emergency
control unit
To silence the alarm from the Emergency Control Unit, press enter
during the re alarm. This will take you to the Silence Alarm screen.
Select ‘Yes’, and enter your access code when requested. During
the re-arming period the following message will be displayed for two
minutes.
Advanced
Emergency Control Unit Operation