Installation and Operation Manual

Page 11 WES
3
Installation and Operations Manual V1.4 Ramtech Electronics Limited 2018
Raising a Medical Alert
The medical alert can be raised from any Emergency Call Point by
pressing and holding the B button for 2 seconds, until the alternating
amber-green LEDs ash repeatedly.
Raising a medical alert sends a message to the Emergency Control
Unit. It does not trigger any alert on other units.
Cancelling a Medical Alert
The medical alert can be cancelled either from the call point used to
create it, or from the Emergency Control Unit.
To cancel from the call point, press and hold the B button for 5
seconds, until the alternating LEDs turn off.
To cancel from the Emergency Control Unit, scroll to the alert on
the Emergency control unit Screen and press enter, scroll to Yes,
then press enter to conrm. The access code is required to cancel a
medical alert. The default PIN number is 1234.
Clear Medical
Assistance From
004F? Yes
WES
3
can receive and display multiple Medical Alerts on the
Emergency Control Unit, and these can be managed and cancelled
individually. Multiple medical alerts are displayed in chronological
order, and prioritised over other system messages except re alarm.
In the event of an emergency alarm being raised while a Medical Alert
is active, the system will give priority to the emergency alarm. Any
Medical Alert that was active prior to the alarm, will remain in the WES
3
system and be displayed once the emergency has been resolved.
Unit Alive Indication
Active units with no faults will ash their green LED once every 4
seconds to indicate that the unit is operational.
Amber LED Indication
Each WES
3
unit monitors itself for a number of faults. These are
indicated via the amber LED, which will ash in grouped patterns with
longer than usual gaps in between them.
Units displaying one of these patterns require further investigation and
should not be relied upon as part of the re alarm and detection system
until the fault has been corrected. Use the chart below to determine the
nature of the issue:
Group Flash 1 - Low Battery
Group Flash 2 - Low signal
Group Flash 3 - Unpaired
Group Flash 4 - Tamper
Group Flash 5 - Re-arm or Unit
latched
Red LED Indication
If a Sensor has raised the alarm, its red LED indicator will ash during
an alarm.
It is recommended that the WES
3
system is tested weekly or whenever
a signicant change has been made to the installation or the building
under construction. WES
3
is equipped with a system test function
that allows you to test the radio link between units without activating
an audible re alarm. You can therefore ensure each unit in the
system has a robust radio link with sufcient capacity to allow for
environmental uctuations without disturbing the site.
SYSTEM WARNINGS
23/06 22:13 004F MED
LED Indications
System Operation