4. Wire Size Selection
All electrical systems lose energy due to resistance in conductors: the wires.
The larger the wire is , the less resistance and the loss are
Resistance losses will also increase with increasing current; therefore, if you installation is at a high wind site, it may be worthwhile to go with a
larger size wire to lower the loss and enhance the output of wind turbine.
Conversely, in low wind sites it may not be cost effective to increase the wire size since power production will be comparative lower.
To determine the wire size, measuring the distance from the batteries to wind turbine is necessary, be sure to include height of the tower. Refer to the
appropriate chart for
your system voltage and select the wire size. The following wire sizes provide maximum annual energy losses of 3% for most
sites.
48V system
Distance from wind generator
to controller
010m 1120m 2130m 3140m 4150m 5160m 6170m 7190m
AWG/Metric Wire Size
mm²
9/6 mm² 9/6 mm² 8/8 mm² 7/10 mm² 6/13 mm² 5/16 mm² 4/21 mm² 4/21 mm²
110 V system
Distance from wind generator
to controller
010m 1120m 2130m 3140m 4150m 5160m 6170m 70100m
AWG/Metric Wire Size
mm²
11/4 mm² 11/4 mm² 11/4 mm² 11/4 mm² 11/4 mm² 9/6 mm² 9/6 mm² 9/6 mm²
220V system
Distance from wind
generator
to controller
010m 1120m 2130m 3140m 4150m 5170m 7190m 91110m
AWG/Metric Wire
Size mm²
11/4 mm² 11/4mm² 11/4 mm² 11/4 mm² 11/4 mm² 11/4 mm² 11/4 mm² 11/4 mm²