Full Product Manual
Install of The Compact Panel Cassette Type Indoor Unit
6
Sponge(attachment)
Clamp(attachment)
Below 0.17in (4mm)
Clamp
Drain hose
Sponge (gray)
Fig.7
Drain stepup pipe note
◆
The install height of the drain raising pipe should less than 11in (280mm).
◆
The drain raising pipe should form a right angle with the unit, and distance to unit should not
beyond 12in (300mm).
Fig.8
Instruction
◆
The slant gradient of the attached drain hose should be within 3in (75mm) so that the drain
hole doesn’t has to endure the unnecessary outside force.
Fig.9
◆
Please install the drain hose according to the following process if several drain hoses join
together.
Fig.10
(2). Check the smoothness of drain after installation.
◆
Check the drain state by immitting 600cc water slowly from the outlet vent or test hole.
◆
Check the drain in the state of refrigerating after installation of the electric circuit.
39-59in
9in (220mm)
11in (280mm)
12in (300mm)
20in (500mm)
20in (500mm)
3in (75mm)