User guide
DS1875
PON Triplexer and SFP Controller
20 ______________________________________________________________________________________
The ADC results (after right-shifting, if used) are com-
pared to high and low alarm and warning thresholds
after each conversion. The alarm values can be used to
trigger the TX-F or FETG outputs. These ADC thresholds
are user programmable through the I
2
C interface, as
well as masking registers that can be used to prevent
the alarms from triggering the TX-F and FETG outputs.
ADC Timing
There are 10 analog channels that are digitized in a
sequential fashion. The MON5–MON8 channels are
sampled depending on the state of the EN5TO8B bit in
Table 02h, Register 89h. If the bit is programmed to
logic 0, the ADC cycles through temperature, V
CC
, and
MON1–MON4 (Figure 5). If the bit is programmed to
logic 1, all 10 channels are digitized, including chan-
nels MON5–MON8 (Figure 6). In this mode (EN5TO8B
= 0), each of MON5–MON8 is sampled on alternate
cycles, as shown in Figure 5. The total time required to
convert one set of channels is the sequential ADC
cycle time, t
FRAME1
or t
FRAME2
(see Figure 6).
Table 3. ADC Default Monitor Ranges
SIGNAL
+FS
SIGNAL
+FS
HEX
-FS
SIGNAL
-FS
HEX
Temperature (°C) 127.996 7FFF -128 8000
V
CC
(V) 6.5528 FFF8 0 0000
MON1–MON8 (V) 2.4997 FFF8 0 0000
V
CC
MON1
MON2 MON3 MON4
MON5 MON6TEMP V
CC
MON1
MON2 MON3 MON4
MON7 MON8TEMP
t
FRAME2
t
FRAME2
Figure 6. ADC Timing with EN5TO8B = 1
TEMP
V
CC
MON1 MON2 MON3 MON4 TEMP
ONE ADC CYCLE
MON4
t
FRAME1
Figure 5. ADC Timing with EN5TO8B = 0
TRIP CONDITION
mCLK
(525kHz)
CAPTURE ALARM
M3QT ALARM
(UNLATCHED)
Figure 4. M3QT Timing










