Check cable continuity
from terminal block to
Sensor Terminal board.
Check and repair cable
continuity from terminal
block to rain gauge.
Contact Factory for
Authorized Repair
Can
+12 Volts DC
be measured at the wind
terminals of the Weather
Station terminal
block?
No
1
Can
+12 Volts DC
be measured at the
terminal block wind
sensor
plug?
Yes
No
End
5
4
6
Reconnect the two wires to the Sensor
Terminal board. At the Weather pole
terminal block, unplug the Wind Sensor
from the connector. Re-measure the
voltage at terminals Input 4(+) and 4(-).
If voltage reads +12 VDC, the problem
is the Wind Sensor. If voltage reads 0,
check for shorts/opens in the cable and
terminal block connections.