8.2.5 Symptom: No Wind Reading
No
1
Check bearings and cup
assembly mounting.
Refer to the Installation
instructions Check and
verify wiring.
Disconnect the two wires
from the Sensor Terminal at
terminals Input 4 (+) and
Input 4 (-) and re-measure
voltage. If voltage reads 0,
contact factory. If voltage
reads +12 VDC, problem lies
in wiring or Wind Sensor.
Start
Does the cup
assembly spin
freely?
Is the
Wind Sensor wired
correctly to the DX2
and the Weather
Computer?
Yes
No
Can
+12 Volts DC
be measured at terminal
Inputs 4+ and 4- of the
Sensor Terminal
board?
Yes
No
1
2
3