Full Product Manual
14
Troubleshooting
Error Detection
The Timer has a built-in error detection that senses an
electrical short circuit or overload condition on a Zone’s
output line.
In the event of an error condition, the following steps
take place regarding the error:
• The aected Zone number and “Err” alert message will
show on the display when the unit is in either AUTO or
MANUAL WATERING mode.
• All irrigation for the aected Zone is cancelled and
watering advances to the next operable Zone in the
irrigation queue.
Electrical Issues
Problem Possible Cause Possible Solution
Display shows error
message “Err M.” Timer
will not activate zones.
Problem with wiring to Master
Valve (if used). There may be
a break in the wire or a loose
connection.
Check wiring and connections to master valve. Repair or
replace wiring and valve if needed. To clear the ashing
error message, press NEXT.
Display is blank. Power not reaching the Timer. Verify the main AC power supply is securely plugged in
or connected and working properly.
Verify the power supply wires are connected to the
Timer “24 VAC” terminals. (Indoor model.)
Display is frozen and
Timer will not accept
programming.
An electrical surge may have
interfered with the Timer’s
electronics.
Unplug the Timer for 2 minutes, then plug it back in. If
there is no permanent damage, the Timer should accept
programming and resume normal operation.
Press and release the RESET button.
NOTE: The Timer will attempt to water the aected
Zone again at the next scheduled watering.
Completion of a successful watering will clear the
error condition associated with that Zone.