Users Manual

Bump Test
The detector can be tested in two ways:
Apply gas from a cylinder to the sensors manually through the calibration cap, and using the
Safety Suite Device Configurator (SSDC) software or the Device Configurator (DC) app.
Use an IntelliDoX module. For further reference see the IntelliDoX User Manual.
CAUTION
Move to a normal atmosphere (20.9% v/v O
2
) that is free of hazardous gas. Use 50% LEL for
test gas.
Details for Bump Test and maintenance:
l Recommendations for initial checking of the equipment on a routine basis including the
maximum time interval between calibrations.
l Perform a functional check with gas before each day of use.
l Honeywell recommends bump testing the sensors before each days use to confirm their
ability to respond to gas by exposing the apparatus to a gas concentration that exceeds the
alarm setpoints. Manually verify that the audible and visual alarms activate.
l The combustible sensor is factory calibrated to 50% LEL methane. If monitoring a different
combustible gas in the % LEL range, calibrate the sensor using the appropriate gas.
Procedure to Bump Test the detector via the calibration cap and the DC app on
a mobile device
1. Turn On the BW Icon. Place the cap over the detector, and then press down on both tabs
to snap it into place. Wait a few minutes to sensors warm up.
BW Icon 19 User Manual