SafetyPractices
ApplicablerequirementsofNationalElectricalCode(NEC),NFPA70;andtheNational
ElectricalSafetyCode,ANSI/IEEEC2,mustbeconsideredduringinstallation.
NOTES:
1.APrimaryProtectorisnotrequiredtoprotecttheexposedwiringaslongastheexposed
wiringlengthislimitedtolessthanorequalto140feet,andinstructionsareprovidedto
avoidexposureofwiringtoaccidentalcontactwithlightningandpowerconductorsin
accordancewithNECSections72554(c)and80030.
Inallothercases,anappropriateListedPrimaryProtectormustbeprovided.RefertoArticles
800and810oftheNECfordetails.
2.ForprotectionofODUagainstdirectlightningstrik es,appropriaterequirementsofNFPA
780shouldbeconsideredinadditiontoNEC.
3.ForCanada,appropriaterequirementsoftheCEC22.1includingSection60andadditional
requirementsofCAN/CSAB72mustbeconsideredasapplicable.