User manual

113
5. [TI] Delay
[3s] Close
valve „Flour ”
Pending for closing the main valve of the
container “Flour”
6. [O] Outputs
Output 11 „1”
Output 11 takes high status („1”) signal
confirming carrying out the dosing making
process on the weighing platform no. 1 is
lit up
7. [F] Set flags
Signal flag 1
„1”
Setting the characteristic point of the
process, which is a condition for carrying
out part of the process on the second
weighing platform
Dosing on the first weighing platform is carried out in two-steps, as for
ingredient „Flour” the outputs are set for two-step dosing see Products
database.
Platform 2
Icon Step Value Description
1. [CF] Flags
condition
Signal flag 1
„1”
Checking condition, whether signal flag 1
is set to value “1” i.e. checking whether
desired part of the process has been
already realized on the weighing platform
no. 1. If Yes, then dosing process on the
weighing platform no. 2 shall start.
2. [CM] Weight
condition
Gross<0.1 kg
Condition checking, unless the weighing
platform is loaded with a mass exceeding
100 g
3. [Z] Zero
Zero
Zeroing the weighing platform no. 2
4. [TI] Delay
[5s] Open valve
Water
Pending for opening main valve of the
container with “Water
5. [DA]
Automatic
batching
2,2 kg [Water]
Automatic dosing of ingredient “Waterto
obtain 2,2 kg mass in single-step dosing
mode Output 6 controls the dosing valve
6. [TI] Delay
[5s] Close valve
Water
Pending for closing the main valve of the
container “Water
7. [O] Outputs
Output 12 „1”
Output 12 takes high status (“1”) signal
confirming carrying out the dosing process
on the weighing platform no. 2 is lit up
8. [TI] Delay
[5s] Dosing
process
completed
Displaying a text message on the terminal
confirming completion of dosing process.
Additionally, in automatic dosing process, additional setting of dosing outputs
for dosed ingredients have to be made see Products database settings.