User manual
113 
5. [TI] Delay 
[3s] Close 
valve „Flour ” 
Pending for closing the main valve of the 
container “Flour”  
6. [O] Outputs 
Output 11 – „1” 
Output 11 takes high status („1”) – signal 
confirming carrying out the dosing making 
process on the weighing platform no. 1 is 
lit up 
7. [F] Set flags 
Signal flag 1 – 
„1” 
Setting the characteristic point of the 
process, which is a condition for carrying 
out part of the process on the second 
weighing platform 
Dosing on the first weighing platform is carried out in two-steps, as for 
ingredient „Flour” the outputs are set for two-step dosing – see Products 
database. 
Platform 2 
Icon  Step  Value  Description 
1. [CF] Flags 
condition 
Signal flag 1 – 
„1” 
Checking condition, whether signal flag 1 
is set to value “1” – i.e. checking whether 
desired part of the process has been 
already realized on the weighing platform 
no. 1. If Yes, then dosing process on the 
weighing platform no. 2 shall start. 
2. [CM] Weight 
condition 
Gross<0.1 kg 
Condition checking, unless the weighing 
platform is loaded with a mass exceeding 
100 g 
3. [Z] Zero 
Zero 
Zeroing the weighing platform no. 2 
4. [TI] Delay 
[5s] Open valve 
Water 
Pending for opening main valve of the 
container with “Water” 
5. [DA] 
Automatic 
batching 
2,2 kg [Water] 
Automatic dosing of ingredient “Water” to 
obtain 2,2 kg mass in single-step dosing 
mode – Output 6 controls the dosing valve  
6. [TI] Delay 
[5s] Close valve 
Water 
Pending for closing the main valve of the 
container “Water” 
7. [O] Outputs 
Output 12 – „1” 
Output 12 takes high status (“1”) – signal 
confirming carrying out the dosing process 
on the weighing platform no. 2 is lit up 
8. [TI] Delay 
[5s] Dosing 
process 
completed 
Displaying a text message on the terminal 
confirming completion of dosing process. 
Additionally, in automatic dosing process, additional setting of dosing outputs 
for dosed ingredients have to be made – see Products database settings.  