User manual
111 
Platform 2: 
Icon  Step  Value  Description 
1. [TI] Delay 
[5s] Place empty 
container 
Pending for loading an empty container for 
the third product (the first product on the 2 
weighing platform) 
2. [CI] Input 
condition 
Input 9 – „/” 
Input 9 has to take increasing tendency – 
press function key confirming loading a 
container 
3. [T] Tare 
Tare 
Tarring the weighing platform no. 2 
4. [DH] Dose 
manually 
0,2 kg 
[Seasoning] 
Manual weighing product “Seasoning”  
to obtain 0,2 kg mass 
5. [TI] Delay 
[5s] Unload 
container with 
product 
Pending for unloading the container with 
weighed product from the weighing platform 
6. [CI] Input 
condition 
Input 12 – „/” 
Input 12 has to take increasing tendency – 
press function key confirming unloading a 
container from the weighing platform 
7. [Z] Zero  Zero  Zeroing the weighing platform no. 2 
8. [CF] Flags 
condition 
Signal flag 1 – „1” 
Checking condition, whether signal flag 1  
is set to value “1” – i.e. checking whether 
desired part of the process has been already 
realized on the weighing platform no. 1.  If 
Yes, then dosing process on the second 
weighing platform shall continue. 
9. [O] Outputs 
Output 1 – „0”, 
Output 12 – „1” 
Output 1 is set to low status – the signal for 
completing dosing process on the weighing 
platfofrm no. 1 is switched off; output 12 
takes the high status – the main water valve 
is opened, for manual dosing of water 
ingredient. 
10. [DH] Dose 
manually 
2 kg [Water] 
Manual weighing product “Water” to obtain 
2kg mass 
11. [O] 
Outputs 
Output 12 – „0” 
Output 12 is set to low status – the main 
water valve is closed 
12. [TI] Delay 
[5s] Unload 
container with 
product 
Pending for unloading the container with 
weighed product from the weighing platform 
13. [CI] Input 
condition 
Input 12 – „/” 
Input 12 can take increasing tendency – 
press function key confirming unloading a 
container from the weighing platform 
14. [O] 
Outputs 
Output 9 – „1” 
Output 9 is set to high status („1”) – signal 
confirming carrying out the dosing process 
on the weighing platform no. 2 is lit up 
15. [TI] Delay 
[5s] Dosing 
process completed 
Displaying a text message on the terminal 
confirming completion of dosing process. 