28.2. Dosing process structure
All activities related to the dosing process can be carried out from
the level of scale. Each dosing process <
> contains:
Its name <
>,
code <
>,
assigned weighing platforms <
> defined on a terminal.
Each of the weighing platforms can have its specific dosing process. The
database of dosing processes has the same searching mechanisms for a
specific record in a database as other terminal databases.
A dosing process can be searched in a database by:
the name of a dosing process < >
the code of a dosing process <
>
Processes carried out on different weighing platforms operated by the same
terminal, can also be dependant on each other, e.g.: dosing on weighing
platform 2 can be initiated only on completing dosing on weighing platform 1,
which is confirmed by a signal from appropriate sensor.
28.3. Local setting of a working mode
Local settings for the working mode < Dosing> are accessible
on pressing a hot key <
Local parameters>:
Ask for multiplier
Causes setting a question for dosing
process multiplier, i.e. the number which is
used to multiply the values of mass of all
components.
Ask for number of cycles
Causes setting a question on number of
dosing process cycles, i.e. number of
repetitions of the same process.
Confirm batching
ingredients manually
Causes enabling manual confirmation by
pressing “Enter/Print” key on terminal’s
keyboard for each weighing process.
No. of weighings for
calculating the correction
Determines the number of recent
measurements which are analyzed for
calculating automatic correction in dosing