Specifications

B
IPMI Commands and Managed Sensors
138
31h +12V RTM
PwrFail
N/A Power problem Monitor to see if the alarm worsens or is persistent
for more than 1 day. If persistent, remove CPM and
contact customer support.
32h +3.3V RTM Fail N/A Power problem Monitor to see if the alarm worsens or is persistent
for more than 1 day. If persistent, remove CPM and
contact customer support.
33h +12V AMC
PwrFail
N/A Power problem Monitor to see if the alarm worsens or is persistent
for more than 1 day. If persistent, remove CPM and
contact customer support.
34h +3.3V AMC Fail N/A Power problem Monitor to see if the alarm worsens or is persistent
for more than 1 day. If persistent, remove CPM and
contact customer support.
35h IOH ThermTrip N/A IOH over temperature event Remove and/or hot swap CPM. If problem persists,
remove CPM and contact customer support.
36h IOH Therm Alert N/A IOH over temperature event Remove and/or hot swap CPM. If problem persists,
remove CPM and contact customer support.
37h DDR Therm T64 N/A Potential thermal problem The board automatically shuts down when any of the
temperature sensors trip the UNR setting on the up
side.
38h CPU CAT ERR N/A CPU catastrophic failure Remove the CPM and contact customer support.
39h AMC PwrFault N/A Power problem Remove the CPM and contact customer support.
3Ah RTM PwrFault N/A Power problem Check the power supply. The problem could be a
hardware issue.
3Bh AMC PCIe PwrEn N/A AMC PCI Express device
improperly enabled or disabled
during hot swap
Check if the AMC is a PCI Express device. Also
check if the device is supported by the CPM via
E-Key.
3Ch RTM PCIe PwrEn N/A RTM PCI Express device
improperly enabled or disabled
during hot swap
Check if the RTM is a PCI Express device. Also
check if the device is supported by the CPM via
E-Key.
3Dh ENET Link 0 N/A Ethernet link sensor does not
report the link status
Check the network configuration, the type of cable,
and the connector.
3Eh ENET Link 1 N/A Ethernet link sensor does not
report the link status
Check the network configuration, the type of cable,
and the connector.
3Fh ENET Link 2 N/A Ethernet link sensor does not
report the link status
Check the network configuration, the type of cable,
and the connector.
40h ENET Link 3 N/A Ethernet link sensor does not
report the link status
Check the network configuration, the type of cable,
and the connector.
41h ENET Link 4 N/A Ethernet link sensor does not
report the link status
Check the network configuration, the type of cable,
and the connector.
42h ENET Link 5 N/A Ethernet link sensor does not
report the link status
Check the network configuration, the type of cable,
and the connector.
AMC sensors: A0h to C7h
RTM sensors: C8h to EFh
N/A
1
Any voltage alarm during CPM bootup keeps the CPM in M3 state. If the CPM has already reached M4 state when the alarm occurs, it
remains in M4 state.
Table 38. Sensor alarms and recommended actions (sheet 14 of 14)
Number Name Alarm level Possible errors or faults Recommendation